Date Code 20100129
Protection and Logic Functions
Port Settings (SET P Command)
Port Settings (SET P Command)
The SEL-751A provides settings that allow you to configure the parameters
for the communications ports. See
for a detailed
description of port connections. On the base unit:
Port F
(front panel) is an
EIA-232 port;
Port 1
is an optional Ethernet port(s);
Port 2
is an optional fiber-
optic serial port; and
Port 3
(rear) is optionally an EIA-232 or EIA-485 port.
On the optional communications card, you can select
Port 4
as either EIA-485
or EIA-232 (not both) with the COMMINF setting. See
through
for the port settings, also see appropriate Appendix for additional
information on the protocol (DNP, MODBUS, IEC-61850, DeviceNet,
Synchrophasors, and M
IRRORED
B
ITS
) of interest.
PORT F
PORT 1
Table 4.51
Time Synchronization Source Setting
Setting Prompt
Setting Range
Setting Name :=
Factory Default
IRIG TIME SOURCE
IRIG1, IRIG2
TIME_SRC := IRIG1
Table 4.52
Front-Panel Serial Port Settings
Setting Prompt
Setting Range
Setting Name :=
Factory Default
PROTOCOL
SEL, MOD, EVMSG,
PMU
PROTO := SEL
SPEED
300–38400 bps
SPEED := 9600
DATA BITS
7, 8 bits
BITS := 8
PARITY
O, E, N
PARITY := N
STOP BITS
1, 2 bits
STOP := 1
PORT TIME-OUT
0–30 min
T_OUT := 5
SEND AUTOMESSAGE
Y, N
AUTO := N
HDWR HANDSHAKING
Y, N
RTSCTS := N
MODBUS SLAVE ID
1–247
SLAVEID := 1
Table 4.53
Ethernet Port Settings
(Sheet 1 of 2)
Setting Prompt
Setting Range
Setting Name :=
Factory Default
IP ADDRESS
zzz.yyy.xxx.www
IPADDR := 192.168.1.2
SUBNET MASK
15 characters
SUBNETM := 255.255.255.0
DEFAULT ROUTER
15 characters
DEFRTR := 192.168.1.1
Enable TCP Keep-Alive
(Y, N)
ETCPKA := Y
TCP Keep-Alive Idle Range
1–20 sec
KAIDLE := 10
TCP Keep-Alive Interval Range
1–20 sec
KAINTV := 1
TCP Keep-Alive Count Range
1–20
KACNT := 6
IMPORTANT:
Upon relay initial
power up or Port 1 setting changes or
Logic setting changes, the user may
have to wait up to two minutes before
an additional setting change can
occur. Note that the relay is functional
with protection enabled, as soon as
the
ENABLED LED
comes ON (about 5—10
seconds from power up).
Содержание 751A
Страница 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Страница 6: ...This page intentionally left blank...
Страница 12: ...This page intentionally left blank...
Страница 18: ...This page intentionally left blank...
Страница 26: ...This page intentionally left blank...
Страница 92: ...This page intentionally left blank...
Страница 218: ...This page intentionally left blank...
Страница 250: ...This page intentionally left blank...
Страница 376: ...This page intentionally left blank...
Страница 392: ...This page intentionally left blank...
Страница 408: ...This page intentionally left blank...
Страница 418: ...This page intentionally left blank...
Страница 434: ...This page intentionally left blank...
Страница 462: ...This page intentionally left blank...
Страница 544: ...This page intentionally left blank...
Страница 580: ...This page intentionally left blank...
Страница 584: ...This page intentionally left blank...
Страница 632: ...This page intentionally left blank...
Страница 636: ...This page intentionally left blank...
Страница 640: ...This page intentionally left blank...