5.21
Date Code 20100129
Instruction Manual
SEL-751A Relay
Metering and Monitoring
Breaker Monitor
10 Percent to 25 Percent Breaker Wear
. The current value changes from 7.0 kA to 2.5 kA. 2.5 kA
is interrupted 290 times (290 close/open operations = 480 – 190), pushing the
breaker maintenance curve from the 10 percent wear level to the 25 percent
wear level.
Compare the 100 percent and 25 percent curves and note that for a given
current value, the 25 percent curve has only 1/4 of the close/open operations
of the 100 percent curve.
Figure 5.21
Breaker Monitor Accumulates 25 Percent Wear
10,000
100%
10%
1000
2
3
4
5
6
7
8
9
100
2
3
4
5
6
7
8
9
10
2
3
4
5
6
7
8
9
1
2
3
4
5
6 7 8 9
50
40
30
20
10
.5
Number of Close/Open Operations
kA Interrupted per Operation
25%
Содержание 751A
Страница 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Страница 6: ...This page intentionally left blank...
Страница 12: ...This page intentionally left blank...
Страница 18: ...This page intentionally left blank...
Страница 26: ...This page intentionally left blank...
Страница 92: ...This page intentionally left blank...
Страница 218: ...This page intentionally left blank...
Страница 250: ...This page intentionally left blank...
Страница 376: ...This page intentionally left blank...
Страница 392: ...This page intentionally left blank...
Страница 408: ...This page intentionally left blank...
Страница 418: ...This page intentionally left blank...
Страница 434: ...This page intentionally left blank...
Страница 462: ...This page intentionally left blank...
Страница 544: ...This page intentionally left blank...
Страница 580: ...This page intentionally left blank...
Страница 584: ...This page intentionally left blank...
Страница 632: ...This page intentionally left blank...
Страница 636: ...This page intentionally left blank...
Страница 640: ...This page intentionally left blank...