4.56
SEL-751A Relay
Instruction Manual
Date Code 20100129
Protection and Logic Functions
Reclose Supervision Logic
If 79CLS is
asserted
to logical 1 at the instant of an open interval time-out,
then the now-qualified open interval time-out will propagate onto the final
close logic in
to automatically reclose the circuit breaker.
If 79CLS is
deasserted
to logical 0 at the instant of an open interval time-out,
the following occurs:
➤
No automatic reclosing takes place.
➤
Relay Word bit RCSF (Reclose Supervision Failure indication)
asserts to logical 1 for one processing interval.
➤
The reclosing relay is driven to Lockout State.
Settings Example 1 on page 4.57
For A Few, Unique Applications (Bottom of
and
For a few unique applications, the Reclose Supervision Limit Time setting is
not
set equal to zero seconds, e.g.,
79CLSD :=
1.00 second
With this setting, the logic in the bottom of
is operative. When an
open interval times out, the SEL
OGIC
control equation reclose supervision
setting 79CLS is then
checked for a time window
equal to setting 79CLSD.
If 79CLS
asserts
to logical 1 at any time during this 79CLSD time window,
then the now-qualified open interval time-out will propagate onto the final
close logic in
to automatically reclose the circuit breaker.
If 79CLS remains
deasserted
to logical 0 during this entire 79CLSD time
window, when the time window times out, the following occurs:
➤
No automatic reclosing takes place.
➤
Relay Word bit RCSF (Reclose Supervision Failure indication)
asserts to logical 1 for one processing interval.
➤
The reclosing relay is driven to Lockout State.
The logic in the bottom of
is explained in more detail in the
following text.
Set Reclose Supervision Logic (Bottom of
)
all
the following are true:
➤
The close logic output CLOSE (also see
) is
not
asserted (Relay Word bit CLOSE = logical 0).
➤
The reclosing relay is
not
in the Lockout State (Relay Word bit
79LO = logical 0).
➤
The circuit breaker is open (52A = logical 0).
➤
The reclose initiation condition (79RI) is
not
making a rising
edge (logical 0 to logical 1) transition.
➤
The Reclose Supervision Limit Timer is
not
timed out (Relay
Word bit RCSF = logical 0).
then a reclosing relay open interval time-out seals in
. Then, when
79CLS asserts to logical 1, the sealed-in reclosing relay open interval time-out
condition will propagate through
and on to the close logic in
.
Содержание 751A
Страница 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Страница 6: ...This page intentionally left blank...
Страница 12: ...This page intentionally left blank...
Страница 18: ...This page intentionally left blank...
Страница 26: ...This page intentionally left blank...
Страница 92: ...This page intentionally left blank...
Страница 218: ...This page intentionally left blank...
Страница 250: ...This page intentionally left blank...
Страница 376: ...This page intentionally left blank...
Страница 392: ...This page intentionally left blank...
Страница 408: ...This page intentionally left blank...
Страница 418: ...This page intentionally left blank...
Страница 434: ...This page intentionally left blank...
Страница 462: ...This page intentionally left blank...
Страница 544: ...This page intentionally left blank...
Страница 580: ...This page intentionally left blank...
Страница 584: ...This page intentionally left blank...
Страница 632: ...This page intentionally left blank...
Страница 636: ...This page intentionally left blank...
Страница 640: ...This page intentionally left blank...