4.104
SEL-751A Relay
Instruction Manual
Date Code 20100129
Protection and Logic Functions
Station DC Battery Monitor
shows the setting prompt, setting range, and factory default settings
for an analog card in Slot
3
.
In this example, assume we want to display the transformer temperature
measurement from Analog Input AI301 (relabeled TX_TEMP) on an
instrument in the station control room that operates on 4–20 mA. We install an
analog output card in Slot
C
, and set the card as shown in
=>>
SET G AO301AQ TERSE <Enter>
Global
AO 301 Settings
AO301 ANALOG QTY (OFF, 1 analog quantity)
AO301AQ := OFF
? AI301 <Enter>
AO301 TYPE (I,V) AO301TYP:= I ?
<Enter>
AO301 AQTY LO (-2147483647.000 to 2147483647.000)
AO301AQL:= 4.000 ?
4 <Enter>
AO301 AQTY HI (-2147483647.000 to 2147483647.000)
AO301AQH:= 20.000 ?
20 <Enter>
AO301 LO OUT VAL (-20.480 to 20.480 mA) AO301L := 4.000 ?
<Enter>
AO301 HI OUT VAL (-20.480 to 20.480 mA) AO301H := 20.000 ?
<Enter>
AO 302 Settings
AO302 ANALOG QTY (OFF, 1 analog quantity)
AO302AQ := OFF
?
END <Enter>
Save changes (Y,N)?
Y <Enter>
Settings Saved
=>>
Figure 4.58
Analog Output Settings
Station DC Battery Monitor
The station dc battery monitor in the SEL-751A can alarm for under- or
overvoltage dc battery conditions and give a view of how much the station dc
battery voltage dips when tripping, closing, and other dc control functions
take place. The monitor function is available with the enhanced voltage option
with monitoring package that includes the 5AVI card in slot E of the relay.
Refer to
Station DC Battery Monitor on page 5.11
for a detailed description
and
for settings.
Table 4.48
Output Setting for a Card in Slot 3
Setting Prompt
Setting Range
Setting Name :=
Factory Default
AO301 ANALOG QTY
Off, 1 analog quantity
AO301AQ := OFF
AO301 TYPE
I, V
AO301TYP := I
AO301 AQTY LO
–2147483647.000 to
+2147483647.000
AO301AQL := 4.000
AO301 AQTY HI
–2147483647.000 to
+2147483647.000
AO301AQH := 20.000
AO301 LO OUT VAL
–20.480 to +20.480 mA
AO301L := 4.000
AO301 HI OUT VAL
–20.480 to +20.480 mA
AO301H := 20.000
AO301 LO OUT VAL
–10.240 to +10.240 V
AO301L := 0.000
a
a
Voltage setting range for a voltage transducer, i.e., when AO301TYP := V
AO301 HI OUT VAL
–10.240 to +10.240 V
AO301H := 10.000
NOTE:
The SEL-751A hides the
following settings with default values
when you use a 3 DI/4 DO/1 AO card:
AOxx1TYP := I
AOxx1L := 4.000
AOxx1H := 20.000
Содержание 751A
Страница 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Страница 6: ...This page intentionally left blank...
Страница 12: ...This page intentionally left blank...
Страница 18: ...This page intentionally left blank...
Страница 26: ...This page intentionally left blank...
Страница 92: ...This page intentionally left blank...
Страница 218: ...This page intentionally left blank...
Страница 250: ...This page intentionally left blank...
Страница 376: ...This page intentionally left blank...
Страница 392: ...This page intentionally left blank...
Страница 408: ...This page intentionally left blank...
Страница 418: ...This page intentionally left blank...
Страница 434: ...This page intentionally left blank...
Страница 462: ...This page intentionally left blank...
Страница 544: ...This page intentionally left blank...
Страница 580: ...This page intentionally left blank...
Страница 584: ...This page intentionally left blank...
Страница 632: ...This page intentionally left blank...
Страница 636: ...This page intentionally left blank...
Страница 640: ...This page intentionally left blank...