TB MRI(K)3-C 03.02 E
Protection parameter
LED
Function
Unit
Default
Actual
settings
settings
Parameter set change-over switch
Set 1/2
Set
P2
Parameter set change-over switch
SET 1
1
2
I>
Pick-up value of the phase overcurrent element
x I
N
0.03
I>+CHAR
Trip characteristics for the phase overcurrent element
DEFT
I>+t> (t
I
>)*
Tripping time (factor) for the phase overcurrent element
(s)
0.04
I>+t> (I>+Fast)*
Fast trip at manual switch on at I>
TIME
I>+CHAR+t>
(tI>+CHAR)*
Reset mode for the tripping characteristics
0s
I>>
Pick-up value for the phase short-circuit element
x I
N
0.50
I>>+t> (t
I
>>)*
Tripping time of the phase short-circuit element
s
0.03
I>>+t> (I>>+Fast)* Fast trip at manual switch on at I>>
TIME
U
E
>
Pick-up value of the residual voltage
V
1V/2V/5V
I
E
>
Pick-up value for earth overcurrent element
xIn(%)**
0.01(0.1)**
I
E
>
Warning/Tripping of the earth current stage
trip
I
E
>+t>+
↔
green
(t
IE
> +
↔
green)*
Tripping time in forward direction
s
0,04
I
E
>+t>+
↔
red
(t
IE
> +
↔
red)*
Tripping time in reverse direction
s
0.04
I
E
>+t> (I
E
>+Fast)*
Fast trip at manual switch on at I
E
>
TIME
I
E
>>
Pick-up value for the earth short-circuit element
xIn(%)**
0.01(0.1)**
IE>>+t>+
↔
green
(tIE>>+
↔
green)*
Tripping time in forward direction
s
0.04
IE>>+t>+
↔
red
(tIE>> +
↔
red)*
Tripping time in reverse direction
s
0.04
I
E
>>+t>
(I
E
>>+Fast)*
Fast trip at manual switch on at I
E
>>
TIME
I
E
>+I
E
>>
Switch over for SIN/COS
SIN
()* LED-Display at MRI3 relay types / ()** Setting at XR-relay types
AR Parameter*
LED
Function
Unit
Default
Actual
settings
settings
Parameter set change-over switch
Satz 1/2
1
2
SHOT
Number of Shots
4
t
F
Fault time t
F
s
0.1
t
D1
Dead time t
D1
s
1.00
t
D2
Dead time t
D2
s
2.00
t
D3
Dead time t
D3
s
2.00
t
D4
Dead time t
D4
s
2.00
t
CI
Close impulse time t
CI
s
0.50
t
R
Reclaim time t
R
s
10.0
t
f
rot + I>+I>> +
I
E
>+I
E
>> green
Fault time activation t
F
1ST
*only MRIK3-relay types