TB MRI(K)3-C 03.02 E
21
4.7.7 Switching on or off the C.B. via the
front panel (LCAL)
After having selected the function (LCAL), pressing the
<SELECT/RESET> key will take you to the control
mode. The display will now show the status of the cir-
cuit breaker C.B.
CB?? Position of the C.B. cannot be established as
the information from the digital inputs is
insufficient. At the same time the LED CB is
flashing. At this stage it is important that a
digital input which has been activated for a
C.B. control function must be used.
(see chapter 5.11.4 and 5.11.5).
A detailed function assignment for the control
signals for the C.B. can be found in Chapter
4.7.9.
ON?? The C.B. is switched off. The LED CB shows a
green light. Press the <ENTER> key and enter
the password to have ON!! shown on the
display.
ON!!
The C.B. can be switched on by pressing the
<ENTER> key.
OFF? The C.B. is switched on. The LED CB shows a
red light. Press the <TRIP> key and enter the
password to have OFF! shown on the
display.
OFF!
The C.B. can be switched off by pressing the
<TRIP> key.
The graph of the procedure of operation assignment
and the C.B. control function can be found in the next
Chapter 4.7.8.