8
TB MRI(K)3-C 03.02 E
3.2
Password
3.2.1 Code jumpers
Behind the front plate of the MR-relays there are three
code jumpers to preset the following functions:
•
Password programming
•
Output relay functions
The following figure shows the position and designa-
tion of the code jumpers:
Figure 3.6: Code jumpers
3.2.2 Password programming
The two different Password are assign to seperate
password sections. Password 1 ( Code jumper 1 )
With this password all protection parameter are
changeable. Password 2 ( Code jumper J2 ) With this
password it is allowed to change the mode of the re-
lay from “remote control” to “local control” and also al-
lowed to control the CB. (See Chap. 4.7.8) The pro-
cedure for password programming is described in
Chapter 4.4 of the description MR - general.
3.2.3 Function of the output relays
The following functions of
MR
output relays can be
preset:
•
Reset of the output relays manually or automati-
cally
The alarm relays are activated according to the preset-
ting:
Code jumper 3 OFF:
All output relays will be reset automatically after the
fault has been rectified, (e.g. when the fault current is
interrupted).
Code jumper 3 ON:
All output relays remains activated and must be reset
after fault clearence.
•
Manually: By pressing push button
<SELECT/RESET>
•
External: By connecting aux. voltage to C8/D8
Via RS 485 interface (see chapter 5.11.4)
To let the parameter change take effect, the auxiliary
voltage has to be switched on and off again after the
code jumpers are plugged or unplugged.
* This functions is only aviable with relays without AR
function ( Type MRI3-C)
Code jumper
Function
Code jumper
position
Operation mode
J1
Password 1**
OFF
Normal position
general
ON
Password selection (see general description MR chapter
4.4)
J2
Password 2**
OFF
Normal position
Control-level
ON
Password selection (see general description MR chapter
4.4)
J3*
Reset
OFF
Output relays will be reset automatically
ON
Output relays will be reset manual/external/via soft-
ware
Table 3.1: Summary of coding possibilities
** are both code jumpers set, it is not possible to change the password.