5.7.5 Release of the pick up relay for CB
failure
protection
This function working similar to the Block / Trip function.
In the case of a fault the function is activated. The pick
up is indicated via a alarm relay to the upstream CB
protection unit. At the upstream CB protection unit the
blocking input is activated. During the clearing of the
fault a CB failure take place, the alarm relay switch off
after the settable CB failure time (Chap 5.7.4) and clear
the block input of the upstream protection unit and acti-
vated the tripping.
I>
+
+
+
tI>
t
1
0
tI>
t
1
0
I>
t
CBFP
Protection Block
Trip
Block
t
1
0
Figure 5.5:
5.8
Interface Parameters
5.8.1 Adjustment of the Slave-Address (RS)
The Slave address can be adjusted in a range from 1-
32.
5.8.2 Adjustment of the Baud-Rate
When the Modbus protocol is used for data transmis-
sion it is possible to adjust different transmission speeds
(Baud rates).
5.8.3 Adjustment of the Parity
For adjustment of the parity there are three options:
•
“even“ = even parity
•
“odd“ = odd parity
•
“no“ = no check of the parity