4.4.12 The unit is programmed for two shots, unsuccessful AR
Figure 4.2: Two shots, AR unsuccessful
Here the time sequence as described in para.4.4.11. The second reclosing shot is however unsuccessful.
4.4.13 Manual closing of the circuit breaker to faulty lines
Short
circuit
Protection
energized
Protection
tripped
Circuit breaker
Switch on
command
Manual on
Protection tripped
Figure 4.3: Manual closing of the C.B. to faulty lines
Unit
MRIK3-C
is in "inactive" status when the circuit
breaker is switched off. When the C.B. is manually
closed the reclaim time is started. In case there is a
faulty line the C.B. is switched off by mains protection
of the relay. After elapse of the reclaim time unit
MRIK3-C
changes over to "inactive" status.