28
TB MRI(K)3-C 03.02 E
5
Operation and Adjustments
5.1
Displayed text for parameter
settings
Function
Displayed Text
Related LED
References
Normal operation
SEG
Exceeding the measuring range
max.
ϑ
Sec.transf.currents indication
SEK
L1, L2, L3,
E
Chap. 5.4.1
Chap. 5.4.2
Rated frequency
f = 50 / f = 60
Chap. 5.4.6
LED flashing after activation
FLSH/NOFL
Chap. 5.4.7
Parameter set change-over switch SET1, SET2,
P2
Chap. 5.4.8
Blocking of a function
EXIT
LED of the blocked
parameter
Characteristics phase current
DEFT,NINV, VINV,
EINV, LINV, RINV,
I> + CHAR
Chap. 5.5.2
Characteristics earth current
DEFT, NINV, VINV,
EINV, LINV, RINV,
RXIDG
IE>> + CHAR
Chap. 5.5.12
Reset mode for phase current
0s / 60s
I> + CHAR + t>
tI> + CHAR*
I> + t
RST
**
Chap. 5.5.5
Reset mode for earth current
0s / 60s
I> + CHAR + t>
I> + t
RST
**
Chap. 5.5.15
Warning or Trip at earth fault
measuring
TRIP/WARN
IE>
Chap. 5.5.11
Measured method of the residual
voltage U
E
1)
E-N; 1:1
Chap. 5.4.3
changeover of isolated (sin
ϕ
) or
compensated (cos
ϕ
) networks
SIN/COS
IE + IE>>
Chap. 5.5.19
CB failure
CB??
CB blinking
Chap. 4.4.7
Auto reclosing successful
Auto reclosing unsuccessful
CLOS
OPEN
0
→
1 rot
Chap. 4.4.6
Chap. 4.4.5
After dead time reclosing condi-
tion
not fulfilled
S/E?
0
→
1 rot
CB blinking
Chap. 4.4.8
Circuit breaker was manually
switched on
MANU
CB rot
Chap. 4.4.2
AR approved
YES/NO
SHOT + I>
SHOT + I>>
SHOT + IE>
SHOT + IE>>
running with
tD1, tD2, tD3, tD4
Chap. 5.11.3
Protection steps blocked
BLOC
I>
I>>
Chap. 5.11.4
Normal trip time
TIME
I
E
>
I
E
>>
Fast trip
FAST
Together
tD1, tD2, tD3, tD4
CB failure protection
CBFP
CB + t>
Chap. 5.7.4
Control functions
LCAL, RMOT
ON??; OFF??; ON!!;
OFF!!
CB
Chap. 4.7.3
Chap. 4.7.7