Secutron Inc.
36
5.6 System Reset Operation
To reset the system, press the ‘Reset System’ button. The panel will remove all power from the
zones and the switched auxiliary relay for 10 seconds. During this 10 second period, the
buzzer will beep twice every 2 seconds.
The panel can only be reset if all waterflow zones are restored (only applies if the Silence
Waterflow option is turned off - see 6.3.5 Waterflow Alarms Programming on page 47).
If the panel is not in a condition to be reset, when the ‘Reset System’ button is pressed the
panel will sound a 1 second error tone on the buzzer.
After the 10 second reset period, the panel will turn off the zone LED for any zones that have
been restored. If one or more zones is still in alarm after the reset period, the panel will
activate the NACs as programmed. If there are no alarms but one or more Supervisory zones
is still ‘off-normal’ after the reset period, the panel will sound the trouble buzzer in the
Supervisory mode. If there are no alarms or supervisory conditions but a trouble is present in
the panel after the reset period, the panel will sound the trouble buzzer. After the reset period,
LEDs for any alarms, supervisory off-normal or trouble conditions will be on.
5.7 Lamp Test
The lamp test will check all of the panel and annunciator LEDs. To do a lamp test, press and
hold the Lamp Test button. All the LEDs will flash.
A lamp test will only work if the NACs are not active and the supervisory buzzer is not active. If
a lamp test is unsuccessful the buzzer will sound a 1 second error tone. If any trouble or zone
has a state change during lamp test, the lamp test will be cancelled and the panel will return to
normal operation.
Содержание MR-2605
Страница 1: ...LT 2016 Rev 4 July 2010 Secutron MR 2605 Five Zone Fire Alarm Control Panel Installation Manual...
Страница 2: ......
Страница 6: ...Secutron Inc vi...
Страница 8: ...Secutron Inc viii...
Страница 10: ...Secutron Inc x...
Страница 70: ...Secutron Inc 70...
Страница 71: ......