Secutron Inc.
55
8
Programming Worksheets
8.1 Entering the Installer Programming Mode
Please see Chapter 6 MR-2605 System Programming on page 39 for complete instructions.
To enter the Installer Programming Mode:
1. Press and hold the
Walk Test
button for two seconds (located behind the display PCB).
2. Press any button to turn off the trouble buzzer.
3. Press
Silence Alarm
to scroll through the settings for each programming section (e.g. to
change the zone type, or to turn an option on or off).
4. Press
Silence Trouble
to move to the next programming section (e.g. to move from zone 1
to zone 2).
5. The panel will indicate the current programming section using the Common Trouble LEDs,
as shown below:
Please see 6.3 Programming Function Descriptions on page 42 for detailed descriptions of
each programming section.
Note:
All zone alarms must be reset prior to entering the Installer Programming Mode. While the panel
is in the Installer Programming Mode, the annunciators will show a trouble condition.