6.3.8 Removing a Module from the System
How to Remove a Modules from the System
1. Physically remove the module from the system and enter the reset section programming as
described above.
2. Enter the Reset Programming Mode as described above.
3. Press the ‘Silence Alarm’ button until the Z1 SUPV LED is ON.
4. Press the ‘Silence Trouble’ button to exit the Reset Programming Mode.The common
trouble buzzer and common trouble LED turn on and pulse ½ second on/off.
5. Press any button to re-enter the Installer Programming Mode. The trouble buzzer is silent
and the zone 1 alarm LED turns on steady. The common trouble LED continues to flash.
You can now cycle through the Installer Programming Mode.
6. To exit immediately, press and hold the Walk Test button for 2 seconds.
7. Upon exit the system will reset the ‘supervision’ field for all the modules currently connected
to the ‘secur-bus.
Table 16 Removing an Module from the System
6.3.9 Adding a Module to the System
Physically connecting the module to the system will allow the module to auto-enroll within one
minute. No additional programming is required.
Panel Status LED
Alarm, Supervisory and
Trouble LED’s
Programmable Setting Description
Removing a Module from the System
CPU
FAULT
Zone 2
Removing
a Module