When installing compatible alarm initiating devices or notification appliances, refer to the
installation documents included with those products.
Field wiring
Field wiring recommendations in this document are intended as guidelines. All field wiring
must be installed in accordance with NFPA 70 National Electrical Code and in Canada with the
standard for installation ULC/S 524, the most current Canadian Electrical Code, with all
relevant local codes and standards, and the Authority Having Jurisdiction.
Compatible devices
Use UL or ULC Listed smoke detectors and notification appliances that are compatible with
the MR-2605 Fire alarm control panel from the lists included in this manual.
1.3 Technical Support and General Information
For technical support call 1--888-SECUTRON, or email [email protected].
For general product information visit the Secutron web site:
www.secutron.com
.
1.4 System Verification
The complete fire alarm system must be verified for proper installation and operation when:
•
the initial installation is ready for inspection by the Local Authority Having Jurisdiction;
•
any system component is added, changed or deleted;
•
any programming changes are made;
•
system wiring has been altered or repaired;
•
system failure due to external influences such as lightning, water damage or extended
power outages has occurred.
1.5 Standby Power
The MR-2605 provides standby battery support for lead-acid rechargeable batteries. The
required capacity of the standby batteries must be calculated using the charts and tables
within this manual for the period as required by national or local codes and standards. Even
though the calculation table within this manual includes a safety margin, lead-acid batteries
commonly used for standby can have variable capacity as a result of age and ambient
conditions. Periodic inspection for damage and the batteries’ ability to support the attached
equipment is highly recommended.
1.6 Battery Maintenance
The two 12V sealed lead-acid batteries should be replaced after each period of 3 to 5 years of
normal service. If the Battery Trouble indicator activates, obtain required service.