5-40
5.2.2
Configuring Alarm Conditions (Threshold Monitoring)
Introduction
The Sebalog D can trigger an alarm whenever a specified minimum or maximum
threshold is crossed.
That way, up to two connected devices (e.g. a pump or a valve) can be triggered by
the internal relays.
Furthermore, alarm messages can be sent via SMS or email, if GSM connectivity
has been established and properly configured (see sections 3.2 and 5.4).
The alarm thresholds must be individually specified for each channel.
Configuring alarms
Perform the following steps to configure the alarm thresholds and the alarm
destinations:
Steps
Action
1
Activate the Alarm active checkbox in order to enable alarming for this
channel.
2
Specify whether there is a minimum and / or a maximum threshold to be
monitored by activating the respective checkbox(es).
3
Enter the minimum and / or the maximum threshold into the respective
field(s).
Specify under Alarm Destinations which of the relays shall switch in the
case of an alarm and which type of alarm message shall be sent.
4
The internal relay of single-channel loggers (LOG D-1) is always
Relay 2!