5-38
5.2.1.2 Input Type Examples
Input type Voltage
A 10 bar pressure sensor with voltage output is connected to a channel of the
logger.
Input type: Voltage 0-5V
Unit:
bar
The lower limit of the measuring range (0 bar) is indicated by a voltage value of 0 V
while the upper limit (10 bar) correlates with 5 V. As a result, the fields must be
populated as follows:
The maximum permissable input voltage is 5 V. Higher input voltages may
damage the device.
Input type Frequency
A level meter with frequency output is installed in a 430 l tank.
Input type: Frequency
Unit:
l
The maximum level of 430 l is indicated by a frequency of 1000 Hz. As a result, the
fields must be populated as follows:
The maximum permissable frequency is 1000 Hz. If the connected sensor
transmits higher frequencies, a frequency divider must be interconnected.