Discharge temperature sensor.
•
Thermistor attached to the discharge line near the compressor. Reported temperature
used by the controller to determine end-of-cycle-fan-off-delay time. If discharge
temperature exceeds a preset maximum, controller will shut the machine off.
Note: Controller will operate machine in a default mode with thermistors disconnected from the
controller. Diagnostic code #5 or 7 will be displayed during that time.
Component Indicator Light Table
System
Indicator Light ON
Condenser Fan or Liquid Line
Valve
Fan Motor Powered or LLV open
Water Pump
Pump Motor Powered
Purge Valve
Purge Valve Opens
Inlet Water Solenoid Valve
Inlet Water Valve Opens
Hot Gas
Hot Gas Valve Opens
Compressor Contactor
Contactor Closes
Ready to Harvest
Water contacting ice thickness sensor probe
Sump Empty
Open between mid sensor and common
Sump Full
Closed between top probe and mid probe
Curtain Switch
Curtain open
September 2006 Page 34
Electrical Component Details
Component Indicator Lights