Remote Condenser Location
Use the following for planning the placement of the condenser relative to the ice machine - see
illustration on the following page.
Location Limits - condenser location must not exceed ANY of the following limits:
•
Maximum rise from the ice machine to the condenser is
35 physical feet
•
Maximum drop from the ice machine to the condenser is
15 physical feet
•
Physical line set maximum length is 100 feet.
•
Calculated line set length maximum is 150.
Calculation Formula:
•
Drop = dd x 6.6 (dd = distance in feet)
•
Rise = rd x 1.7 (rd = distance in feet)
•
Horizontal Run = hd x 1 (hd = distance in feet)
•
Calculation: Drop(s) + Rise(s) + Horizontal Run = dd+rd+hd = Calculated Line Length
Configurations that do NOT meet these requirements must receive prior written
authorization from Scotsman.
Do NOT:
•
Route a line set that rises, then falls, then rises.
•
Route a line set that falls, then rises, then falls.
Calculation Example 1:
The condenser is to be located 5 feet below the ice machine and then 20 feet away
horizontally.
5 feet x 6.6 = 33. 33 + 20 = 53. This location would be acceptable
Calculation Example 2:
The condenser is to be located 35 feet above and then 100 feet away horizontally. 35 x 1.7 =
59.5. 59.5 +100 = 159.5. 159.5 is greater than the 150 maximum and is NOT acceptable.
Operating a machine with an unacceptable configuration is misuse and will void the
warranty.
September 2006 Page 13
General Installation - Remote
Содержание C0522SR-1
Страница 96: ...Wiring Diagram C0522R C0530R C0630R C0830R C1030R Single Phase after 9 09 September 2009 Page 96 ...
Страница 98: ...Wiring Diagram C0522R C0530R C0630R C0830R C1030R Three Phase after 9 09 September 2009 Page 98 ...
Страница 126: ...Wiring Diagram C0630R 6 C0830R 6 C1030R 6 September 2009 ...
Страница 127: ...Wiring Diagram C0830R 63 C1030R 63 September 2009 ...