12.3
Date Code 20080213
Instruction Manual
SEL-351A Relay
Standard Event Reports and SER
Standard 15/30-Cycle Event Reports
Programmable SEL
OGIC
Control Equation Setting ER
The programmable SEL
OGIC
control equation event report trigger setting ER
is set to trigger standard event reports for conditions other than trip conditions.
When setting ER sees a logical 0 to logical 1 transition, it generates an event
report (if the SEL-351A is not already generating a report that encompasses
the new transition). The factory setting is:
ER =
/51P + /51G + /OUT103
The elements in this example setting are:
➤
51P Maximum phase current above pickup setting 51PP for
phase time-overcurrent element 51PT (see
).
➤
51G Residual-ground current above pickup setting 51GP for
residual-ground time-overcurrent element 51GT (see
➤
OUT103 Output contact
OUT103
is set as a breaker failure trip
output (see
Note the rising-edge operator / in front of each of these elements. See
for more information on
rising-edge operators and SEL
OGIC
control equations in general.
Rising-edge operators are especially useful in generating an event report at
fault inception and then generating another later if a breaker failure condition
occurs. For example, at the inception of a ground fault, pickup indicator 51G
asserts and an event report is generated:
ER =
... + /51G + ...
= logical 1 (for one processing interval)
Even though the 51G pickup indicator will remain asserted for the duration of
the ground fault, the rising-edge operator / in front of 51G (/51G) causes
setting ER to be asserted for only one processing interval.
If the fault is not interrupted after the relay trips, then the relay outputs a
breaker failure trip with output contact
OUT103
and another event report is
generated:
ER =
... + /OUT103
= logical 1 (for one processing interval)
As stated earlier, the 51G pickup indicator is still asserted at the time of
breaker failure trip, but the rising-edge operators allow each individual action
to generate a separate event report.
Falling-edge operators \ are also used to generate event reports. See
for more information on falling-edge operators.
TRI (Trigger Event Report) and PUL (Pulse Output Contact) Commands
The sole function of the
TRI
serial port command is to generate standard
event reports, primarily for testing purposes.
The
PUL
command asserts the output contacts for testing purposes or for
remote control. If output contact
OUT101
–
OUT107
asserts via the
PUL
command,
the relay triggers a standard event report. The
PUL
command is available at
the serial port and the relay front-panel
{CNTRL}
pushbutton.
Section 10: Serial Port Communications and Commands
and
Front-Panel Interface (Only on Models With LCD)
) for more
information on the
TRI
(Trigger Event Report) and
PUL
(Pulse Output
Contact) commands.
Содержание SEL-351A
Страница 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 16: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 34: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 126: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 184: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 198: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 228: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 278: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 384: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 410: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 450: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 454: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 472: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 504: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 558: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 562: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 586: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 608: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 666: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...