6.14
SEL-351A Relay
Instruction Manual
Date Code 20080213
Close and Reclose Logic
Reclosing Relay
➤
Reclose initiation is unsuccessful because of SEL
OGIC
control
equation setting 79RIS [see
Initiate Supervision Settings (79RI and 79RIS, respectively) on
page 6.19
].
➤
The circuit breaker opens without reclose initiation (e.g., an
external trip).
➤
The shot counter is equal to or greater than last shot, and the
circuit breaker is open. [For instance, the shot counter could be
driven to last shot with SEL
OGIC
control equation setting
79DLS while open interval timing is in progress. [See
Lockout and Drive-to-Last Shot Settings (79DTL and 79DLS,
respectively) on page 6.21
➤
The close failure timer (setting CFD) times out (see
).
➤
SEL
OGIC
control equation setting 79DTL = logical 1 [see
Drive-to-Lockout and Drive-to-Last Shot Settings (79DTL and
79DLS, respectively)
].
➤
The Reclose Supervision Limit Timer (setting 79CLSD) times
out (see
) and the reclose
enable setting, E79, has setting choices 1, 2, 3, or 4.
➤
A new reclose initiation occurs while the reclosing relay is
timing on an open interval (e.g., flashover in the tank while
breaker is open).
Relay Word bit OC asserts for execution of the
OPEN
command. See
Command (Open Breaker) on page 10.35
OPEN
command. Also, see
Drive-to-Lockout and Drive-to-Last Shot Settings
(79DTL and 79DLS, respectively)
If the
OPEN
command is set to trip (TR = … + OC; see Note following
), then the following reclosing relay SEL
OGIC
control equation
settings should also be made (presuming that an
OPEN
command trip should
not initiate reclosing):
79RI =
TRIP
(reclose initiate)
79DTL =
… + OC
(drive-to-lockout)
This is how the SEL-351A is set at the factory.
Reclosing Relay
States and Settings/
Setting Group
Changes
If individual settings are changed for the active setting group or the active
setting group is changed,
all
of the following occur:
➤
The reclosing relay remains in the state it was in before the
settings change.
➤
The shot counter is driven to last shot (last shot corresponding
to the new settings; see discussion on last shot that follows).
➤
The reset timer is loaded with reset time setting 79RSLD (
).
If the relay happened to be in the Reclose Cycle State and was timing on an
open interval before the settings change, the relay would be in the Reclose
Cycle State after the settings change, but would immediately go to the
Lockout State. This is because the breaker is open, and the relay is at last shot
after the settings change, so no more automatic reclosures are available.
NOTE:
The
OPEN
command is
included in the reclosing relay logic
via the factory SEL
OGIC
control
equation settings:
79DTL = … + OC (drive-to-lockout)
Содержание SEL-351A
Страница 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 16: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 34: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 126: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 184: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 198: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 228: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 278: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 384: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 410: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 450: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 454: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 472: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 504: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 558: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 562: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 586: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 608: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 666: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...