7.21
Date Code 20080213
Instruction Manual
SEL-351A Relay
Inputs, Outputs, Timers, and Other Control Logic
Multiple Setting Groups
In this example, timer SV8T is used in both setting groups; different timers
could have been used with the same operational result. The timers reset during
the setting group change, allowing the same timer to be used in both setting
groups.
Timer pickup setting SV8PU is set greater than the pulse width of the SCADA
contact (
). This allows only one active setting group change (e.g.,
from setting Group 1 to 4) for each pulse of the SCADA contact (and
subsequent assertion of input
IN105
). The function of the SEL
OGIC
control
equations in
becomes more apparent in the following example
scenario.
Start Out in Setting Group 1
.
The relay has been in setting Group 1 for some time, with timer logic output
SV8T asserted to logical 1, thus enabling SEL
OGIC
control equation setting
SS4 for the assertion of input
IN105
.
Switch to Setting Group 4
and
The SCADA contact pulses input
IN105
, and the active setting group changes
to setting Group 4 after qualifying time setting TGR (perhaps set at a cycle or
so to qualify the assertion of setting SS4). Optoisolated input
IN105
also has its
own built-in debounce timer (IN105D) available (see
).
shows both setting Group 1 and setting Group 4
settings. The setting Group 1 settings (top of
) are enabled only
when setting Group 1 is the active setting group and likewise for the setting
Group 4 settings at the bottom of the figure.
Setting Group 4 is now the active setting group, and Relay Word bit SG4
asserts to logical 1. After the relay has been in setting Group 4 for a time
period equal to SV8PU, the timer logic output SV8T asserts to logical 1, thus
enabling SEL
OGIC
control equation setting SS1 for a new assertion of input
IN105
.
Note that input
IN105
is still asserted as setting Group 4 is activated. Pickup
time SV8PU keeps the continued assertion of input
IN105
from causing the
active setting group to revert back again to setting Group 1 for a single
assertion of input
IN105
. This keeps the active setting group from being
changed at a time interval less than time SV8PU.
Switch Back to Setting Group 1
.
The SCADA contact pulses input
IN105
a second time, and the active setting
group changes back to setting Group 1 after qualifying time setting TGR
(perhaps set at a cycle or so to qualify the assertion of setting SS1).
Optoisolated input
IN105
also has its own built-in debounce timer (IN105D)
available (see
).
Содержание SEL-351A
Страница 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 16: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 34: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 126: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 184: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 198: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 228: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 278: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 384: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 410: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 450: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 454: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 472: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 504: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 558: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 562: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 586: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 608: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 666: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...