G.9
Date Code 20080213
Instruction Manual
SEL-351A Relay
Setting SEL
OGIC
Control Equations
SEL
OGIC
Control Equations
and an instantaneous trip results. This logic is commonly used in fuse-saving
schemes for distribution feeders.
If the reclosing relay shot counter advances to shot = 1 for the reclose that
follows the trip, Relay Word bit SH0 is in the following state:
SH0 =
0
(logical 0)
If maximum phase current is
above
the phase instantaneous overcurrent
element pickup setting 50P1P for the reoccurring fault, Relay Word bit 50P1
is in the following state:
50P1 =
1
(logical 1)
With SH0 = 0 and 50P1 = 1, the ANDed combination results in:
50P1 * SH0 =
1 * 0
= 0 (logical 0)
and no trip results from phase instantaneous overcurrent element 50P1.
A trip will eventually result if time-overcurrent element 51PT or 51GT times
out. If residual-ground time-overcurrent element 51GT times out, Relay Word
bit 51GT is in the following state:
51GT =
1
(logical 1)
When shot = 1, SH0 = 0 and the result is:
TR =
51PT + 51GT + 50P1 * SH0
= 0 + 1 + 1 * 0 = 0 + 1 + 0 = 1
and a time-delayed trip results from residual-ground time-overcurrent element
51GT.
Set an Output Contact for Tripping
To assert output contact
OUT101
to trip a circuit breaker, make the following
SEL
OGIC
control equation output contact setting (see
OUT101 =
TRIP
All SEL
OGIC
Control
Equations Must Be
Set
All SEL
OGIC
control equations must be set one of the following ways (they
cannot be “blank”):
➤
Single Relay Word bit (e.g., 52A = IN101)
➤
Combination of Relay Word bits (e.g., TR = 51PT + 51GT +
50P1 * SH0)
➤
Directly to logical 1 (e.g., 67P1TC = 1)
➤
Directly to logical 0 (e.g., TRCOMM = 0)
Set SEL
OGIC
Control Equations Directly to 1 or 0
SEL
OGIC
control equations can be set directly to:
1 (logical 1) or 0 (logical 0)
instead of with Relay Word bits. If a SEL
OGIC
control equation setting is set
directly to 1, it is always “asserted/on/enabled.” If a SEL
OGIC
control equation
setting is set equal to 0, it is always “deasserted/off/disabled.”
Under the
SHO Command (Show/View Settings) on page 10.25
, note that a
number of the factory SEL
OGIC
control equation settings are set directly to 1
or 0.
NOTE:
SEL
OGIC
control equation
torque control settings (e.g., 67P1TC,
51P1TC) cannot be set directly to
logical 0.
Содержание SEL-351A
Страница 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 16: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 34: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 126: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 184: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 198: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 228: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 278: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 384: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 410: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 450: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 454: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 472: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 504: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 558: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 562: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 586: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 608: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 666: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...