8.17
Date Code 20080213
Instruction Manual
SEL-351A Relay
Breaker Monitor and Metering
Station DC Battery Monitor (Not in SEL-351A-1)
Output Contact Type Considerations (a or b)
(especially Note 2 in
Consider the output contact type (a or b) needed for output contact
OUT106
in
the bottom of
(dc voltage alarm example).
If SEL
OGIC
control equation setting OUT106 is asserted (OUT106 = SV4T =
logical 1; dc voltage OK), the state of output contact
OUT106
(according to
contact type) is:
➤
closed (a-type output contact)
➤
open (b-type output contact)
If SEL
OGIC
control equation setting OUT106 is deasserted (OUT106 = SV4T
= logical 0; dc voltage
not
OK), the state of output contact
OUT106
(according
to contact type) is:
➤
open (a-type output contact)
➤
closed (b-type output contact)
If the relay loses power entirely, all output contacts deassert, and the state of
output contact
OUT106
(according to contact type) is:
➤
open (a-type output contact)
➤
closed (b-type output contact)
Additional
Application
Other than alarming, the dc voltage elements can be used to disable reclosing.
For example, if the station dc batteries have a problem and the station dc
battery voltage is declining, drive the reclosing relay to lockout:
79DTL =
!
SV4T + ...
[= NOT(SV4T) + ...]
Timer output SV4T is from the bottom of
. When dc voltage falls
below pickup DCHIP, timer output SV4T drops out (= logical 0), driving the
relay to lockout:
79DTL =
!SV4T + ...
= NOT(SV4T) + ... = NOT(logical 0) + ... = logical 1
Circuit breaker tripping and closing require station dc battery energy. If the
station dc batteries are having a problem and the station dc battery voltage is
declining, the relay should not reclose after a trip because there might not be
enough dc battery energy to trip a second time after a reclose.
View Station DC
Battery Voltage
Via Serial Port
MET Command (Metering Data) on page 10.18
. The
MET
command
displays the station dc battery voltage (labeled VDC).
Via Front Panel (Only on Models With LCD)
The information available via the previously discussed
MET
serial port
command is also available via the front-panel
{OTHER}
pushbutton. See
.
Содержание SEL-351A
Страница 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 16: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 34: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 126: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 184: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 198: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 228: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 278: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 384: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 410: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 450: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 454: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 472: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 504: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 558: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 562: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 586: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 608: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 666: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...