5.13
Date Code 20080213
Instruction Manual
SEL-351A Relay
Trip and Target Logic
Front-Panel Target LEDS
Other Applications for the {TARGET RESET/LAMP TEST} Function
. The combination of the
{TARGET RESET}
pushbutton and the
TAR R
(Target Reset) serial port command is available as
Relay Word bit TRGTR. Relay Word bit TRGTR pulses to logical 1 for one
processing interval when either the
{TARGET RESET}
pushbutton is pushed or the
TAR R
(Target Reset) serial port command is executed.
Relay Word bit TRGTR can be used to unlatch logic. For example, refer to the
breaker failure logic in
. If a breaker failure trip occurs (SV7T
asserts), the occurrence can be displayed on the front panel with seal-in logic
and a rotating default display (see
Rotating Default Display (Only on Models
and
Rotating Default Display on page 11.12
):
SV8 =
(SV8 + SV7T) * !TRGTR
DP3 =
SV8
DP3_1 =
BREAKER FAILURE
DP3_0 =
NA
(blank)
Figure 5.4
Seal-in of Breaker Failure Occurrence for Message Display
If a breaker failure trip has occurred, the momentary assertion of SV7T
(breaker failure trip) will cause SV8 in
to seal-in. Asserted SV8 in
turn asserts DP3, causing the message:
to display in the rotating default display.
This message can be removed from the display rotation by pushing the
{TARGET RESET}
pushbutton (Relay Word bit TRGTR pulses to logical 1,
unlatching SV8 and in turn deasserting DP3). Thus, front-panel rotating
default displays can be easily reset along with the front-panel targets by
pushing the
{TARGET RESET}
pushbutton.
SEL
OGIC
Control
Equation Setting
FAULT
SEL
OGIC
control equation setting FAULT has control over or is used in the
following:
➤
Front-panel target LEDs
INST
,
A
,
B
, and
C
. See
➤
Demand Metering—FAULT is used to suspend demand
metering peak recording. See
.
➤
Maximum/Minimum Metering—FAULT is used to block
Maximum/Minimum metering updating. See
SV7T
Breaker Failure Trip
(= logical 1)
(= logical 0)
Target Reset
TRGTR
SV8
DP3 = SV8
DP3_1 = BREAKER FAILURE
DP3_0 = (blank)
BREAKER FAILURE
NOTE:
Display Points are only
available on relay models with an LCD.
Содержание SEL-351A
Страница 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 16: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 34: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 126: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 184: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 198: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 228: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 278: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 384: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 410: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 450: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 454: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 472: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 504: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 558: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 562: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 586: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 608: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 666: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...