10.17
Date Code 20080213
Instruction Manual
SEL-351A Relay
Serial Port Communications and Commands
Command Explanations
To display the relay event summaries, enter the following command:
=>
HIS <Enter>
FEEDER 1 Date: 08/10/99 Time: 08:40:16.740
STATION A
# DATE TIME EVENT LOCAT CURR FREQ GRP SHOT TARGETS
1 02/01/99 08:33:00.365 TRIG $$$$$$$ 1 60.00 3 2
2 01/31/99 20:32:58.361 ER $$$$$$$ 231 60.00 2 2
3 01/29/99 07:30:11.055 AG T 9.65 2279 60.00 3 2 INST 50
=>
The fault locator has influence over information in the
EVENT
and
LOCAT
columns. If the fault locator is enabled (enable setting EFLOC = Y), the fault
locator will attempt to run if the event report is generated by a trip (assertion
of TRIP Relay Word bit) or other programmable event report trigger condition
(SEL
OGIC®
control equation setting ER).
If the fault locator runs successfully, the location is listed in the
LOCAT
column,
and the event type is listed in the
EVENT
column:
If a trip occurs in the same event report, a
T
is appended to the event type (e.g.,
AG T
).
If the fault locator does not run successfully,
$$$$$$$
is listed in the
LOCAT
column. If the fault locator is disabled (enable setting EFLOC = N), the
LOCAT
column is left blank. For either of these cases where the fault locator does not
run, the event type listed in the
EVENT
column is one of the following:
Relay
Response
Definition
AG
for A-phase to ground faults
BG
for B-phase to ground faults
CG
for C-phase to ground faults
AB
for A-B phase-to-phase faults
BC
for B-C phase-to-phase faults
CA
for C-A phase-to-phase faults
ABG
for A-B phase-to-phase to ground faults
BCG
for B-C phase-to-phase to ground faults
CAG
for C-A phase-to-phase to ground faults
ABC
for three-phase faults
A
for A-phase faults (Petersen Coil or
Ungrounded/High-Impedance Grounded Systems only)
B
for B-phase faults (Petersen Coil or
Ungrounded/High-Impedance Grounded Systems only)
C
for C-phase faults (Petersen Coil or
Ungrounded/High-Impedance Grounded Systems only)
Relay
Response
Definition
TRIP
event report generated by assertion of Relay Word bit TRIP
ER
event report generated by assertion of
SEL
OGIC
control equation event report trigger condition setting ER
Содержание SEL-351A
Страница 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 16: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 34: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 126: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 184: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 198: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 228: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 278: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 384: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 410: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 450: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 454: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 472: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 504: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 558: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 562: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 586: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 608: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 666: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...