42
S
YSTEM
O
N DIRECT COMMAND
Close the mains input switch (SWIN), the bypass input switch (SWBYP)
if present, and the battery fuse holder (SWBATT).
Check that the display turns on and the UPS enters into the "STAND-BY
WITH CB OFF" mode.
Verify that
the Mains and the Bypass input voltages on the “System
measurements” page are present.
Check that no error messages appear (except “Output Switch open”).
Press the “Menu” icon
and select the “Command launcher” icon
.
Tap the “SYSTEM ON” command and press OK to confirm.
Wait for a few seconds and check that the UPS turns on with the output
powered by the inverter. The buzzer should start and the system status
should read DISCONNECTED FROM THE LOAD. This indicates that
the output switch (SWOUT) is not closed and the load is not supplied.
From the
menu select the “bell” icon
if you want to silence the
alarm.
Close the Output switch to supply the load and check that the inverter is
correctly powering it.
Verify on the home page that system
operating mode is “ON LINE”.
Check the Output parameters in the Output status page.
Check the battery status (if present) and verify the measurements.
Set the Date and Time,
Enter the “General and System setting” menu
.
Tap the “Display” icon
and set the desired value in the Date/Time
page.
Store the new settings by pressing the “Save” icon.
In order to return to the main page, press the “HOME” icon.