Error management
©
by Antriebs- & Regeltechnik Schimpf GmbH
65
For example, the system checks whether the 4 mA calibration value is lower than the
20 mA calibration value for the analogue interface. It does not, however, check if the 4
mA calibration value is within the range of 8 mA.
Troubleshooting
Error
Possible cause
Solution
“Ready for operation”
relay is not active
The drive is in
configuration mode
Change to standard mode
The drive is in “idle”
mode, “manual
movement” mode or
“manual movement,
ignore limit switch” mode
Change to another mode
No supply voltage to the
drive
Check the connection cables
for the supply voltage
Excess heat: The
temperature in the drive
is over 70°C.
Let the drive cool down.
Analogue input line break Check the connection cables
of the analogue input
Motor error (e.g.
blockage)
Check the drive as well as the
actuator for a blockage.
If necessary, increase the
“Torque” setting.
If necessary, increase the
“Ramp” setting.
Check whether the end
positions are set correctly.
Check the actuator for dirt or
deposits.
The position is outside
the permitted range
Return the position to the
permitted range in manual
mode.
Содержание 00-10/30 STEP
Страница 28: ...Connections by Antriebs Regeltechnik Schimpf GmbH 28 Figure 10 CPU board 00 15 Figure 11 Add on board 00 15 ...
Страница 69: ...Declaration of Conformity by Antriebs Regeltechnik Schimpf GmbH 69 Declaration of Conformity ...
Страница 71: ...Dimensional drawing by Antriebs Regeltechnik Schimpf GmbH 71 Figure 15 Dimensions of drive type 00 15 ...
Страница 72: ...Dimensional drawing by Antriebs Regeltechnik Schimpf GmbH 72 Figure 16 Dimensions of drive type 01 15 ...