P746/EN OP/G31
Operation
(OP) 5-
8
MiCOM
P746
1.3.2
Circuit Breaker Fail (CBF)
The detailed logic of the circuit breaker failure element follows.
The P746 hardware corresponds to up to 6 circuit breaker and can accommodate 1 or 2 trip
coils per breaker (depending on relay number, defined by P746 model number, and PSL(CB
trip signal connection to the relay output)).:
•
1 main trip coil
•
1 back-up trip coil
Furthermore these can be either 3 single-phase trip coils or 1 three-phase trip coil. These
can be combined for example 3 single-phase trip coils on the main system and 1 three-
phase trip coil for the back-up system.
1.3.2.1 Circuit Breaker Fail Reset Criteria
1.3.2.1.1 Overcurrent Criterion
One of the most common causes of busbar mal-tripping is error introduced in the back
tripping of adjacent sections. To prevent such an error it is possible to condition the
operation of 50BF protection only when there is presence of a significant current i.e. a short-
circuit on the concerned feeder. This confirmation is provided by the
I
> threshold which is set
by default at 1.2 times the nominal rated current of the CT.
OP
1.3.2.1.2 Undercurrent reset Criterion
The criterion normally used for the detection of a circuit breaker pole opening is the
disappearance of the current i.e. undercurrent element. This function is generally preferred
above other elements due to its very fast response time. In P746, this method of detection is
used and has the threshold
I
<.
for phase A.
Note:
The same algorithm is used for the other phases.
This Undercurrent elements have an I< threshold, which is used to supervise that each
circuit breaker has opened correctly, when commanded to do so. By use of the I< threshold,
it is possible to ensure that all load and fault current has been ruptured, ensuring that no
arcing remains across the circuit breaker primary contacts. Optionally, the user can decide to
include 52a supervision in the breaker fail logic (see chapters 1.3.2.1.3 and 1.3.2.1.4).
Note :
– 52a is the setting name, it means CB closed.
– The CB closed position is created in the PSL either using 52b
reversed or a combination of (52a and 52b).
The first function is to compare the current sample to the I< threshold and check for the
following sequence:
•
positive value of the current
•
no current (below the threshold)
•
negative value of the current
•
no current (below the threshold)
•
positive value of the current
•
…
The output signal is pl(t), it changes between 0 and 1.
Internal overcurrent signals are available per phase and neutral to confirm that the CB failure
algorithm has started to count down.
Содержание MiCOM P746
Страница 4: ......
Страница 5: ...Pxxx EN SS G11 SAFETY SECTION...
Страница 6: ......
Страница 8: ...Pxxx EN SS G11 Page 2 8 Safety Section BLANK PAGE...
Страница 16: ...P746 EN IT G31 Introduction MiCOM P746...
Страница 18: ...P746 EN IT G31 Introduction IT 1 2 MiCOM P746 IT BLANK PAGE...
Страница 26: ...P746 EN TD G31 Technical Data MiCOM P746...
Страница 38: ...P746 EN GS G31 Getting Started MiCOM P746...
Страница 78: ...P746 EN ST G31 Getting Started MiCOM P746...
Страница 80: ...P746 EN ST G31 Settings ST 4 2 MiCOM P746 ST BLANK PAGE...
Страница 112: ...P746 EN ST G31 Settings ST 4 34 MiCOM P746 ST BLANK PAGE...
Страница 114: ...P746 EN OP G31 Operation MiCOM P746...
Страница 136: ...P746 EN OP G31 Operation OP 5 22 MiCOM P746 OP BLANK PAGE...
Страница 138: ...P746 EN AP G31 Application Notes MiCOM P746...
Страница 142: ...P746 EN AP G31 Application Notes AP 6 4 MiCOM P746 AP BLANK PAGE...
Страница 194: ...P746 EN AP G31 Application Notes AP 6 56 MiCOM P746 AP BLANK PAGE...
Страница 196: ...P746 EN PL G31 Programmable Logic MiCOM P746...
Страница 238: ...P746 EN MR A11 Measurements and Recording MiCOM P746...
Страница 240: ...P746 EN MR A11 Measurements and Recording MR 8 2 MiCOM P746 MR BLANK PAGE...
Страница 258: ...P746 EN FD G31 Firmware Design MiCOM P746...
Страница 280: ......
Страница 342: ...P746 EN CM F21 Commissioning and Maintenance CM 10 62 MiCOM P746 CM Commissioning Engineer Customer Witness Date Date...
Страница 348: ...P746 EN MT A11 Maintenance MiCOM P746...
Страница 350: ...P746 EN MT A11 Maintenance MT 11 2 MiCOM P746 MT BLANK PAGE...
Страница 364: ...P746 EN MT A11 Maintenance MT 11 16 MiCOM P746 MT BLANK PAGE...
Страница 366: ...P746 EN TS G31 Troubleshooting MiCOM P746...
Страница 368: ...P746 EN TS G31 Troubleshooting TS 12 2 MiCOM P746 TS BLANK PAGE...
Страница 382: ...P746 EN SC G31 SCADA Communications MiCOM P746...
Страница 424: ...P746 EN SC G31 SCADA Communications SC 13 42 MiCOM P746 SC BLANK PAGE...
Страница 426: ...P746 EN SG F21 Symbols and Glossary MiCOM P746...
Страница 438: ......
Страница 440: ...P746 EN IN G31 Installation IN 15 2 MiCOM P746 IN BLANK PAGE...
Страница 465: ...Installation P746 EN IN G31 MiCOM P746 IN 15 27 IN 10P74611 1 FIGURE 18 MiCOM P746 80TE WIRING DESCRIPTION P746xxxL...
Страница 468: ......
Страница 470: ...P746 EN HI G31 Remote HMI HI 16 2 MiCOM P746 HI BLANK PAGE...
Страница 500: ...P746 EN HI G31 Remote HMI HI 16 32 MiCOM P746 HI BLANK PAGE...
Страница 502: ......
Страница 504: ...P746 EN CS A11G31 Cyber Security CS 17 2 MiCOM P746 CS BLANK PAGE...
Страница 524: ...P746 EN VH G31 Firmware and Service Manual Version History MiCOM P746...
Страница 529: ......