P746/EN ST/G31
Settings
(ST) 4-
24
MiCOM
P746
ST
Menu Text
Default Setting
Available Settings
Contact Test
No Operation
No Operation, Apply
Test, Remove Test
When the ‘Apply Test’ command in this cell is issued the contacts set for operation (set to
‘1’) in the ‘Test Pattern’ cell change state. After the test has been applied the command text
on the LCD will change to ‘No Operation’ and the contacts will remain in the Test State until
reset issuing the ‘Remove Test’ command. The command text on the LCD will again revert
to ‘No Operation’ after the ‘Remove Test’ command has been issued.
Note: When the ‘Test Mode’ cell is set to ‘Enabled’ the ‘Relay O/P Status’ cell does not
show the current status of the output relays and hence can not be used to confirm
operation of the output relays. Therefore it will be necessary to monitor the state
of each contact in turn.
Test LEDs
No Operation
No Operation
Apply Test
When the ‘Apply Test’ command in this cell is issued the eighteen user-programmable
LEDs will illuminate for approximately 2 seconds before they extinguish and the command
text on the LCD reverts to ‘No Operation’.
Red LED Status
000001000100000000
This cell is an eighteen bit binary string that indicates which of the user-programmable
LEDs on the relay are illuminated with the Red LED input active when accessing the relay
from a remote location, a ‘1’ indicating a particular LED is lit and a ‘0’ not lit.
Green LED Status
000001000100000000
This cell is an eighteen bit binary string that indicates which of the user-programmable
LEDs on the relay are illuminated with the Green LED input active when accessing the relay
from a remote location, a ‘1’ indicating a particular LED is lit and a ‘0’ not lit.
Test Zone
none
None / Zone1 / Zone2 /
Zone 1 and Zone2
The Test Zone cell is used to block a zone for test. It disables the 50BF protection and block
all the tripping relays connected to the blocked zone(s). Alarm LED is lit.
DDB 31 - 0
00000000000000000000000000000000
Displays the status of DDB signals 0 – 31.
DDB 2047 - 2016
00000000000000000000000000000000
Displays the status of DDB signals 2047 – 2016.
1.3.8 Opto
configuration
Setting Range
Menu Text
Default Setting
Min. Max.
Step Size
OPTO CONFIG.
Global Nominal V
48/54V
24/27V, 30/34V, 48/54V, 110/125V,
220/250V, Custom
Sets the nominal battery voltage for all opto inputs by selecting one of the five standard
ratings in the Global Nominal V settings. If Custom is selected then each opto input can
individually be set to a nominal voltage value.
Opto Filter Ctrl
11111111111111111111111111111111
This menu is used to control the relay’s opto-isolated inputs L1 to L32. A ‘1’ indicates an
energized and operating relay, a ‘0’ indicates a de-energized
Opto Filter Ctrl2
11111111
Controls the next relay’s opto-isolated inputs (L33 to L40).
Содержание MiCOM P746
Страница 4: ......
Страница 5: ...Pxxx EN SS G11 SAFETY SECTION...
Страница 6: ......
Страница 8: ...Pxxx EN SS G11 Page 2 8 Safety Section BLANK PAGE...
Страница 16: ...P746 EN IT G31 Introduction MiCOM P746...
Страница 18: ...P746 EN IT G31 Introduction IT 1 2 MiCOM P746 IT BLANK PAGE...
Страница 26: ...P746 EN TD G31 Technical Data MiCOM P746...
Страница 38: ...P746 EN GS G31 Getting Started MiCOM P746...
Страница 78: ...P746 EN ST G31 Getting Started MiCOM P746...
Страница 80: ...P746 EN ST G31 Settings ST 4 2 MiCOM P746 ST BLANK PAGE...
Страница 112: ...P746 EN ST G31 Settings ST 4 34 MiCOM P746 ST BLANK PAGE...
Страница 114: ...P746 EN OP G31 Operation MiCOM P746...
Страница 136: ...P746 EN OP G31 Operation OP 5 22 MiCOM P746 OP BLANK PAGE...
Страница 138: ...P746 EN AP G31 Application Notes MiCOM P746...
Страница 142: ...P746 EN AP G31 Application Notes AP 6 4 MiCOM P746 AP BLANK PAGE...
Страница 194: ...P746 EN AP G31 Application Notes AP 6 56 MiCOM P746 AP BLANK PAGE...
Страница 196: ...P746 EN PL G31 Programmable Logic MiCOM P746...
Страница 238: ...P746 EN MR A11 Measurements and Recording MiCOM P746...
Страница 240: ...P746 EN MR A11 Measurements and Recording MR 8 2 MiCOM P746 MR BLANK PAGE...
Страница 258: ...P746 EN FD G31 Firmware Design MiCOM P746...
Страница 280: ......
Страница 342: ...P746 EN CM F21 Commissioning and Maintenance CM 10 62 MiCOM P746 CM Commissioning Engineer Customer Witness Date Date...
Страница 348: ...P746 EN MT A11 Maintenance MiCOM P746...
Страница 350: ...P746 EN MT A11 Maintenance MT 11 2 MiCOM P746 MT BLANK PAGE...
Страница 364: ...P746 EN MT A11 Maintenance MT 11 16 MiCOM P746 MT BLANK PAGE...
Страница 366: ...P746 EN TS G31 Troubleshooting MiCOM P746...
Страница 368: ...P746 EN TS G31 Troubleshooting TS 12 2 MiCOM P746 TS BLANK PAGE...
Страница 382: ...P746 EN SC G31 SCADA Communications MiCOM P746...
Страница 424: ...P746 EN SC G31 SCADA Communications SC 13 42 MiCOM P746 SC BLANK PAGE...
Страница 426: ...P746 EN SG F21 Symbols and Glossary MiCOM P746...
Страница 438: ......
Страница 440: ...P746 EN IN G31 Installation IN 15 2 MiCOM P746 IN BLANK PAGE...
Страница 465: ...Installation P746 EN IN G31 MiCOM P746 IN 15 27 IN 10P74611 1 FIGURE 18 MiCOM P746 80TE WIRING DESCRIPTION P746xxxL...
Страница 468: ......
Страница 470: ...P746 EN HI G31 Remote HMI HI 16 2 MiCOM P746 HI BLANK PAGE...
Страница 500: ...P746 EN HI G31 Remote HMI HI 16 32 MiCOM P746 HI BLANK PAGE...
Страница 502: ......
Страница 504: ...P746 EN CS A11G31 Cyber Security CS 17 2 MiCOM P746 CS BLANK PAGE...
Страница 524: ...P746 EN VH G31 Firmware and Service Manual Version History MiCOM P746...
Страница 529: ......