63
SCAIME Manual : NU-eNod4C-E-0418-196712-F.docx
Defective measurement outputs parameters (Available depending on version)
Changes Defective measurement outputs timing.
An internal alarm flag reflects the integrity of the
whole measurement chain. It’s used to set logical
output active or optional analog output in an error
mode in order to warn about any defection on the
measurement chain (defective measurement).
This variable is set active when at least one of the
followings conditions occurs:
-
sensor input control results out of
tolerances
-
sensor input control command in progress
-
sensor input control command failed
(timeout)
-
sensor input reference command in
progress
-
gross meas. < (- max capacity)
-
gross meas. > (max capacity)
-
analog signal out of the A/D converter
input range
-
EEPROM failure
This internal alarm flag is featured with adjustable
specific de-bounced time and minimal activation time:
Defective
measurement
debounced time
0
–
65535 ms
The internal alarm flag which reflects the integrity of the whole
measurement chain is set active only after error conditions have
always been true during this de-bounced time.
Defective
measurement
alarm activation
time
0
–
65535 ms
The internal alarm flag which reflects the integrity of the whole
measurement chain remains active for this minimal
“defective
measurement alarm activation time”
when it come to be active
and whatever the error conditions are during activation.
12.1.5.5
Configuration setup
Содержание eNod4-C BOX
Страница 8: ...8 SCAIME Manual NU eNod4C E 0418 196712 F docx 3 GENERAL CHARACTERISTICS 3 1 Dimensions ...
Страница 9: ...9 SCAIME Manual NU eNod4C E 0418 196712 F docx ...
Страница 14: ...14 SCAIME Manual NU eNod4C E 0418 196712 F docx 4 CONNECTIONS ...
Страница 64: ...64 SCAIME Manual NU eNod4C E 0418 196712 F docx Parameter Possible Value Description Metrology Parameters ...