S1-02: DC Injection Current at Start
Determines the amount of current to use for DC Injection at the start. Set as a percentage of the motor
rated current.
No.
Parameter Name
Setting Range
Default
S1-02
DC Injection Current at Start
0 to 100%
100%
■
S1-03: DC Injection Current at Stop
Determines the amount of current to use for DC Injection at the stop. Set as a percentage of the motor
rated current.
No.
Parameter Name
Setting Range
Default
S1-03
DC Injection Current at Stop
0 to 100%
100%
■
S1-04: DC Injection / Position Lock Time at Start
Determines how long the drive should perform DC Injection at the start. During this time, the drive
allows motor flux to develop, which is essential for applying torque quickly once the brake is
released. A setting of 0.00 disables S1-04.
No.
Parameter Name
Setting Range
Default
S1-04
DC Injection Time at Start
0.00 to 10.00 s
0.40 s
■
S1-05: DC Injection / Position Lock Time at Stop
Determines how long the drive should perform DC Injection at the stop. A setting of 0.00 disables S1-
05.
No.
Parameter Name
Setting Range
Default
S1-05
DC Injection Time at Stop
0.00 to 10.00 s
0.60 s
■
S1-06: Brake Release Delay Time
Determines the time that must pass after an Up/Down command is entered before the output terminal
set for "Brake control" is triggered. Adjusting this delay time can help when there is not enough time
to develop the appropriate amount of motor flux. Be sure to also increase the time S1-04 when setting
S1-06 to relatively long delay time.
No.
Parameter Name
Setting Range
Default
S1-06
Brake Release Delay Time
0.00 to 10.00s
0.20 s
■
S1-07: Brake Close Delay Time
Determines the time that must pass after zero speed is reached before the output terminal set for
"Brake control" is released.
No.
Parameter Name
Setting Range
Default
S1-07
Brake Close Delay Time
0.00 to 10.00s
0.30 s
■
S1-10: Run Command Delay Time
Sets the time the drive waits after receiving an Up/Down command before starting operation. The
time set should give the motor contactor enough time to close.
No.
Parameter Name
Setting Range
Default
S1-10
Run Command Delay Time
0.00 to 1.00 s
0.20s
■
S1-11: Output Contactor Open Delay Time
Determines the time that must pass for an output terminal set for “Output contactor control” to be
released after the drive has stopped and drive output has been shut off.