12
5.
The display automatically returns to the display in
Step 1.
6.
Repeat Steps 1 through 5 to set the following
parameters:
• T1-03, Motor Rated Voltage
• T1-04, Motor Rated Current
• T1-05, Motor Base Frequency
• T1-06, Number of Motor Poles
• T1-07, Motor Base Speed
• T1-08, Encoder Resolution
■
Starting Auto-Tuning
WARNING!
Electrical Shock Hazard. High voltage will be supplied to the motor when Stationary
Auto-Tuning is performed even with the motor stopped, which could result in death or serious
injury. Do not touch the motor until Auto-Tuning has been completed.
Step
Display/Result
1.
After entering the data listed on the motor nameplate,
press
to confirm.
2.
Press
to activate Auto-Tuning.
3.
Auto-Tuning finishes in approximately five seconds.
Parameter Settings during Induction Motor Auto-Tuning: T1
The T1-
**
parameters are used to set the Auto-Tuning input data for induction motor tuning.
■
T1-01: Auto-Tuning Mode Selection
Sets the type of Auto-Tuning to be used.
No.
Parameter Name
Setting Range
Default
T1-01
Auto-Tuning Mode Selection
3
3
Setting 3: Stationary Auto-tuning