Hardware Manual for the PCD2.M5 Series│Document 26/856; Version EN 12│2014-07-24
Saia-Burgess Controls AG
Communication interfaces
5
5-15
Serial interfaces - Slots A1 and A2
5.4.5 MP-Bus with PCD7.F180, Port#1 & Port#2
PCD7.F180:
Connection module to MP-Bus
The user can connect an MP-Bus line with 8 drives and sensors.
Connections
PCD7.F180
PCD7.F180
10
11
12
13
14
15
16
17
18
19
0
1
2
3
4
5
6
7
8
9
11, (1) MP
12, (2) ,MFT’
13, (3) ,IN’
14, (4) GND
10, (0) -
15, (5) -
1, (1) MP
2, (2) ,MFT’
3, (3) ,IN’
4, (4) GND
0, (0) -
5, (5) -
Socket A1
Socket A2
x3, Port 2
x4, Port 1
MP-Bus signal line (18V in/out)
MFT-Parametrie device (MP-Bus intern)
MFT-Parametrie device detection (Input 10 kOhm, Z5V1)
Ground connection MFT-Parametrie device
GND (A-)
GND
MP-Bus signal line (18V in/out)
MFT-Parametrie device (MP-Bus intern)
MFT-Parametrie device detection (Input 10 kOhm, Z5V1)
Ground connection MFT-Parametrie device
GND (A-)
GND
There are the following parameterization devices of BELIMO
®
:
Manual Control Unit
MFT-H
With its own power supply/batteries
PC-Tool
MFT-P
With the adapter ZIP-RS-232
Supply option
Common supply for control and drive
+
–
11
PCD2
13
10
18
19
14
15
16
17
-
/D
D
+
WD
-
-
+
+
12
L
N
L N
±20%
driv
es
MFT P
ar
ametrie de
vic
e
P
ort #1
Controller
24 VDC