Connection concept for two-wire transducers
E1
E0
GND
PCD2.W310/340
0...20 mA
4...20 mA*
ρ
ϑ
24 VDC
Pressure
Tempera-
ture
Input filter
+
E2
*4...20 mA over user program
Two-wire transducers need a 24 VDC-supply in the measuring trunk.
Block diagram
E0
E1
E2
E3
E4
E5
E6
E7
GND
R
source
Voltage
Source
10.000V
Ref.
Voltage
2.500V
Input filter and amplifier
MUX
A
D
Data
I/O Bus
PCD Bus
+5V
GND
/IOOUIT
IODIN
/IOWRITE
IODOUT
I/MS0
IOA0
IOA1
IOA2
IOA3
W340, W350, W360 only
Programming
Classic:
Programming examples
for the PCD2.W3x0 can be found on the TCS
Support site (
www.saia-support.com
+ getting started).
xx7:
The firmware reads in the values according to the configuration (I/O
Builder)
●
Watchdog: This module cannot be used on the base address 240, because it
would interact with the watchdog, and would cause a malfunction.
● For details, please refer to the "Watchdog" section, which describes the correct