EQJW 125: Heating controller
Communication functions
50
7001029003 A
© Fr. Sauter AG
In the case of a modem connection, before executing write commands via
Modbus, the valid code number (123) must be written to Modbus register
40145. Otherwise, only read commands will be processed. This is used to
prove the legitimacy of the management system.
If an incorrect code number is entered three times via Modbus, this is
recorded as a prohibited access attempt. As the result, an error bit is set and
the control station is dialled by the controller.
6.4.2
Sending SMS if there is a fault on the plant
A modem enables the controller to send an error message to a mobile phone
as an SMS message. As soon as a fault is registered in the device status
register of the controller, an SMS message is sent. This requires modem
access from a provider (SMSC = Short Message Service Centre) which
accepts SMS messages in TAP protocol. The message on the display of the
mobile phone will then read something like this:
'Heating controller EQJW 125 / Device status:
[XXXX] / Note: 0 = no error; >0 = error has occurred'
The value shown for the device status corresponds to the value of SERVice
parameter SP02. The error that has occurred is stored in this value in
encoded form (see Section 6). The SMS Centre usually sends the date, time
and sender's telephone number for this message.
Access numbers for SMSC
:
D1 network of Deutsche Telekom:
0171 2521002
ditto via ISDN using X.75:
0171 2521001
O
2
Germany:
0179 7673425
E-PLUS Germany:
0177 1167
Cellnet (GB)
0044 7860980480
To enable the function, CP02 must be set to 4 (or 5) and the telephone
numbers of the provider and the mobile phone must be entered at CP07 and
CP08. (see section 3.3).
4
No guarantee is given of the availability and correctness of these numbers. Up-to-
date information on this subject must be requested from the network operator.
Содержание Equitherm EQJW 125
Страница 1: ......
Страница 2: ...EQJW 125 Heating controller User s Manual 7001029003 A R ...
Страница 7: ...EQJW 125 Heating controller Table of contents 6 7001029003 A Fr Sauter AG ...
Страница 9: ...EQJW 125 Heating controller Symbols used in this manual 8 7001029003 A Fr Sauter AG ...
Страница 11: ...EQJW 125 Heating controller General information 10 7001029003 A Fr Sauter AG ...
Страница 15: ...EQJW 125 Heating controller Description of the controls 14 7001029003 A Fr Sauter AG ...
Страница 20: ...EQJW 125 Heating controller Commissioning 7001029003 A Fr Sauter Ltd 19 ...
Страница 58: ...EQJW 125 Heating controller Economy tips 7001029003 A Fr Sauter Ltd 57 ...
Страница 60: ...EQJW 125 Heating controller Resistance values for the Ni1000 sensors 7001029003 A Fr Sauter Ltd 59 ...
Страница 62: ...EQJW 125 Heating controller Dimension drawing 7001029003 A Fr Sauter Ltd 61 ...