EQJW 125: Heating controller
Commissioning
28
7001029003 A
© Fr. Sauter AG
Parameter
Description
Range
Step
Value
CP17
–
SMS or MOD bus via modem:
automatic configuration of modem
0 = not enabled; 1 = enabled
0…1
1
CP18
5
SMS or MOD BUS via modem:
dialling pause in minutes
0...255
1
CP19
5
SMS or MOD BUS via modem:
time-out in minutes
1…255
1
CP20
5
SMS or MOD bus via modem:
number of dialling attempts
1…255
1
CP21
0
SMS or MOD bus via modem:
send message even if error is rectified
0 = not enabled; 1 = enabled
0…1
1
CP22
0
SMS via modem:
select language for error message
0 = German;
1 = French;
2 = English;
3 = Italian;
4 = Spanish
0…4
1
CP23
0
MOD bus via modem:
disable dialling control station in case of fault
0 = not enabled; 1 = enabled
0…1
1
CP24
0
MOD bus via RS485 or MOD bus via modem:
control station commands
expire after control station is inactive for 30 minutes
0 = not enabled; 1 = enabled
0…1
1
Tab. 2: Communication parameters
3.3.5
Explanations of communication parameters
Serial number
The serial number of the controller can be shown.
Type of communication
The type of communication can be set. You can choose from these options:
0 = no communication
1 = device bus
2 = MOD bus via RS485
3 = MOD bus via modem
4 = SMS via modem
5 = MOD bus and SMS via modem
CP 01
CP02
Содержание Equitherm EQJW 125
Страница 1: ......
Страница 2: ...EQJW 125 Heating controller User s Manual 7001029003 A R ...
Страница 7: ...EQJW 125 Heating controller Table of contents 6 7001029003 A Fr Sauter AG ...
Страница 9: ...EQJW 125 Heating controller Symbols used in this manual 8 7001029003 A Fr Sauter AG ...
Страница 11: ...EQJW 125 Heating controller General information 10 7001029003 A Fr Sauter AG ...
Страница 15: ...EQJW 125 Heating controller Description of the controls 14 7001029003 A Fr Sauter AG ...
Страница 20: ...EQJW 125 Heating controller Commissioning 7001029003 A Fr Sauter Ltd 19 ...
Страница 58: ...EQJW 125 Heating controller Economy tips 7001029003 A Fr Sauter Ltd 57 ...
Страница 60: ...EQJW 125 Heating controller Resistance values for the Ni1000 sensors 7001029003 A Fr Sauter Ltd 59 ...
Страница 62: ...EQJW 125 Heating controller Dimension drawing 7001029003 A Fr Sauter Ltd 61 ...