EQJW 125: Heating controller
Commissioning
7001029003 A
© Fr. Sauter Ltd.
31
SMS or Modbus via modem: number of dialling attempts
The dialling attempts via modem to the provider or the control station are
repeated, observing the dialling pause (CP18), if the line is busy or if it is
impossible to make a connection for any other reason. When the number of
dialling attempts set at CP 20 is reached, however, no further attempts are
made at first and the modem status is shown as 'OFF'. The dialling attempts
counter is automatically reset at 12:00 hours and then the dialling attempts
to the BMS are made again.
SMS or Modbus via modem: send message even if error is rectified
If CP21 is set to 1, dialling will also take place if the fault has been rectified
and the controller is operating without faults again.
SMS via modem: language for error messages
This parameter is used to select the language that is used to send an SMS.
The numbers have the following meanings:
0 = German; 1 = French; 2 = English; 3 = Italian; 4 = Spanish
Modbus via modem: disable fault dialling
If CP23 is set to 1, there are no dialling attempts via modem to the BMS if a
fault occurs.
Modbus via RS485 or Modbus via modem: control station commands expire
after the control station has been inactive for 30 minutes
When CP24 = 1: if the controller is no longer receiving any Modbus enquiries,
operating statuses specified via Modbus become invalid after 30 minutes and
the controller operates independently of the control station again. If CP24 = 0,
the operating statuses continue to have unlimited validity even beyond these
30 minutes.
CP20
CP21
CP22
CP23
CP24
Содержание Equitherm EQJW 125
Страница 1: ......
Страница 2: ...EQJW 125 Heating controller User s Manual 7001029003 A R ...
Страница 7: ...EQJW 125 Heating controller Table of contents 6 7001029003 A Fr Sauter AG ...
Страница 9: ...EQJW 125 Heating controller Symbols used in this manual 8 7001029003 A Fr Sauter AG ...
Страница 11: ...EQJW 125 Heating controller General information 10 7001029003 A Fr Sauter AG ...
Страница 15: ...EQJW 125 Heating controller Description of the controls 14 7001029003 A Fr Sauter AG ...
Страница 20: ...EQJW 125 Heating controller Commissioning 7001029003 A Fr Sauter Ltd 19 ...
Страница 58: ...EQJW 125 Heating controller Economy tips 7001029003 A Fr Sauter Ltd 57 ...
Страница 60: ...EQJW 125 Heating controller Resistance values for the Ni1000 sensors 7001029003 A Fr Sauter Ltd 59 ...
Страница 62: ...EQJW 125 Heating controller Dimension drawing 7001029003 A Fr Sauter Ltd 61 ...