EQJW 125: Heating controller
Commissioning
7001029003 A
© Fr. Sauter Ltd.
29
Baud rate (BAUD)
Transmission speed between BMS and controller or (for modem operation)
transmission speed between controller and modem. Must match the Baud
rate of the BMS.
Device bus address
This is used for the unique identification of the controller on the device bus.
Each address must be assigned only once, and a device in the controller
grouping must have address 1.
Modbus address
This address is used to identify the controllers for RS485 or modem
operation. Each address must occur only once within a system.
Modbus via modem: phone number of the control station
The telephone number of the BMS modem must be entered here, including
the dialling code or (for example) a 0 for extension systems. Short pauses
between the digits can be entered with P (= 1 second), and the end of the
number is identified by '–'. The phone number can comprise a maximum of
22 digits (including pauses).
SMS via modem: telephone number of the provider
The telephone number for the provider's SMS forwarding service must be
entered here, including the dialling code or (for example) a 0 for extension
systems. Short pauses between the digits can be entered with P (= 1
second), and the end of the number is identified by '–'. The phone number
can comprise a maximum of 22 digits (including pauses). When selecting the
provider, make sure that TAP (Telocator Alphanumeric Protocol) is used.
SMS via modem: telephone number of the mobile phone
The telephone number of the mobile phone must be entered here, including
the complete dialling code (e.g. 00 41 ...). The phone number can comprise a
maximum of 22 digits.
Device bus: time synchronisation
If CP 09 is set to 1, this controller sends time information on the device bus
every 24 hours. All devices with CP 09 set to 0 will evaluate this information
and set their clocks accordingly. Within a controller grouping, this function
should only be active on one controller, whose time will then be set on each of
the other controllers.
Device bus: send outdoor temperature
If CP 10 is set to 1, this controller sends the current outdoor temperature on
the device bus.
CP03
CP04
CP05
CP06
CP07
CP08
CP09
CP10
Содержание Equitherm EQJW 125
Страница 1: ......
Страница 2: ...EQJW 125 Heating controller User s Manual 7001029003 A R ...
Страница 7: ...EQJW 125 Heating controller Table of contents 6 7001029003 A Fr Sauter AG ...
Страница 9: ...EQJW 125 Heating controller Symbols used in this manual 8 7001029003 A Fr Sauter AG ...
Страница 11: ...EQJW 125 Heating controller General information 10 7001029003 A Fr Sauter AG ...
Страница 15: ...EQJW 125 Heating controller Description of the controls 14 7001029003 A Fr Sauter AG ...
Страница 20: ...EQJW 125 Heating controller Commissioning 7001029003 A Fr Sauter Ltd 19 ...
Страница 58: ...EQJW 125 Heating controller Economy tips 7001029003 A Fr Sauter Ltd 57 ...
Страница 60: ...EQJW 125 Heating controller Resistance values for the Ni1000 sensors 7001029003 A Fr Sauter Ltd 59 ...
Страница 62: ...EQJW 125 Heating controller Dimension drawing 7001029003 A Fr Sauter Ltd 61 ...