EQJW 125: Heating controller
Application
7001029003 A
© Fr. Sauter Ltd.
55
8.2
General information
This application requires an additional safety thermostat.
Before the plant is commissioned, the slope of the characteristic and the flow
temperature limit must be checked in every case.
Depending on the application, the following settings are recommended:
characteristic slope
SERVice parameter SP17
value 1.4 (
)
flow temperature limit
SERVice parameter SP16
value 75°C (
)
characteristic slope
SERVice parameter SP17
value 0.6
flow temperature limit
SERVice parameter SP16
value 50°C
The recommended values have been tried and tested but they are not
necessarily the ideal solutions for every plant. No liability is accepted for the
values indicated here.
CAUTION!
Radiator heating
Floor heating
Содержание Equitherm EQJW 125
Страница 1: ......
Страница 2: ...EQJW 125 Heating controller User s Manual 7001029003 A R ...
Страница 7: ...EQJW 125 Heating controller Table of contents 6 7001029003 A Fr Sauter AG ...
Страница 9: ...EQJW 125 Heating controller Symbols used in this manual 8 7001029003 A Fr Sauter AG ...
Страница 11: ...EQJW 125 Heating controller General information 10 7001029003 A Fr Sauter AG ...
Страница 15: ...EQJW 125 Heating controller Description of the controls 14 7001029003 A Fr Sauter AG ...
Страница 20: ...EQJW 125 Heating controller Commissioning 7001029003 A Fr Sauter Ltd 19 ...
Страница 58: ...EQJW 125 Heating controller Economy tips 7001029003 A Fr Sauter Ltd 57 ...
Страница 60: ...EQJW 125 Heating controller Resistance values for the Ni1000 sensors 7001029003 A Fr Sauter Ltd 59 ...
Страница 62: ...EQJW 125 Heating controller Dimension drawing 7001029003 A Fr Sauter Ltd 61 ...