EQJW 125: Heating controller
Communication functions
46
7001029003 A
© Fr. Sauter AG
Number of
holding
register
Description
Comment
Read
only
Decimal
points
Units
With
math.
sign?
40146
Cycl_Init_Modem
Modem - cyclical initialisation
no
0
min
no
40147
DialPause_Modem
Modem - dialling pause after engaged tone
no
0
min
no
40148
DialRpt_Modem
Modem - number of dialling attempts
no
0
no
40149
Time-out_Modem
Watchdog, 'Modem time constant'
no
0
min
no
40150
Device statusReg
Device status register
yes
0
no
40152
ErrorstatArchiv
Device status archive
no
0
no
40154
ErrorCounterReg
Error counter register
no
0
no
41000
FlowSetp_Rk1
Flow setpoint
no
1
°C
yes
41001
MaxFlow_Rk1
Maximum flow temperature
no
1
°C
yes
41002
MinFlow_Rk1
Minimum flow temperature
no
1
°C
yes
41003
Day_Setp_Rk1
Setpoint, normal mode
no
1
°C
yes
41004
Night_Setp_Rk1
Setpoint, reduced mode
no
1
°C
yes
41006
Slope_HeatCh_Rk1
Slope of heating characteristic
no
1
no
41065
Kp_Rk1(Y1)
Proportional band
no
1
no
41066
Tn_Rk1(Y1)
Reset time
no
0
sec
no
41067
Ty_Rk1
Run-time for actuator
no
0
sec
no
42000 to
42047
Switching
commands
48 possible switching commands for the 1
st
heating circuit
no
0
no
42500 to
42519
Calendar switching
program
20 possible switching commands for the
calendar switching program
no
0
no
Tab. 3: Modbus data points
The data points are transmitted in 16 bits.
Содержание Equitherm EQJW 125
Страница 1: ......
Страница 2: ...EQJW 125 Heating controller User s Manual 7001029003 A R ...
Страница 7: ...EQJW 125 Heating controller Table of contents 6 7001029003 A Fr Sauter AG ...
Страница 9: ...EQJW 125 Heating controller Symbols used in this manual 8 7001029003 A Fr Sauter AG ...
Страница 11: ...EQJW 125 Heating controller General information 10 7001029003 A Fr Sauter AG ...
Страница 15: ...EQJW 125 Heating controller Description of the controls 14 7001029003 A Fr Sauter AG ...
Страница 20: ...EQJW 125 Heating controller Commissioning 7001029003 A Fr Sauter Ltd 19 ...
Страница 58: ...EQJW 125 Heating controller Economy tips 7001029003 A Fr Sauter Ltd 57 ...
Страница 60: ...EQJW 125 Heating controller Resistance values for the Ni1000 sensors 7001029003 A Fr Sauter Ltd 59 ...
Страница 62: ...EQJW 125 Heating controller Dimension drawing 7001029003 A Fr Sauter Ltd 61 ...