EQJW145: Heating controller
Communication functions
7010015003 A
71
© Fr. Sauter AG
Number of
holding
register
Description
Comment
Read
only
Decimal
points
Units With math.
Sign?
40108
Mode_Rk2
1=Auto, 2=Stdby, 3=Manual, 4=Sun,
5=Moon
no
0
no
40109
ControlSignal_Rk2
Opening for control signal Rk2
[0...100%]
no 0
% no
40117
AT_HeatOff_Rk1
Value TA heating switch-off
no
1
°C
yes
40145
Write-En_Modem
Write enable for modem
(code number input)
no
0
no
40146
Cycl_Init_Modem
Modem - cyclical initialisation
no
0
min
no
40147
DialPause_Modem
Modem - dialling pause after engaged
tone
no
0
min
no
40148
DialRpt_Modem
Modem - number of dialling attempts
no
0
no
40149
Timeout_Modem
Watchdog, 'Modem time constant'
no
0
min
no
40150
Device statusReg
Device status register
yes
0
no
40152
ErrorstatArchiv
Device status archive
no
0
no
40154
ErrorCounterReg
Error counter register
no
0
no
41000
FlowSetp_Rk1
Flow setpoint
no
1
°C
yes
41001
MaxFlow_Rk1
Maximum flow temperature
no
1
°C
yes
41002
MinFlow_Rk1
Minimum flow temperature
no
1
°C
yes
41003
Day_Setp_Rk1
Setpoint - normal mode
no
1
°C
yes
41004
Night_Setp_Rk1
Setpoint - reduced mode
no
1
°C
yes
41006
Slope_HeatCh_Rk1
Slope of heating characteristic
no
1
no
41065
Kp_Rk1
Proportional band
no
1
no
41066
Tn_Rk1
Reset time
no
0
sec
no
41067
Ty_Rk1
Running time for actuator
no
0
sec
no
41800
WW setpoint increased
Setpoint WW for thermal disinfection
(20°C…90°C)
no
1
°C
no
41807
WW setpoint normal
Setpoint WW in normal case
(20°C…90°C)
no
1
°C
no
41865
Kp_Rk2
Proportional band (2nd heating circuit)
no
1
no
41866
Tn_Rk2
Reset time (2nd heating circuit)
no
0
sec
no
41867
Ty_Rk2
Running time for actuator (2nd heating
circuit)
no
0
sec
no
Содержание EQJW145
Страница 1: ...EQJW145 Heating controller Operating manual 7010015003 A R ...
Страница 8: ...EQJW145 Heating controller Symbols used in this manual 8 7010015003 A Fr Sauter AG ...
Страница 10: ...EQJW145 Heating controller General information 10 7010015003 A Fr Sauter AG ...
Страница 46: ...EQJW145 Heating controller Commissioning 46 7010015003 A Fr Sauter AG ...
Страница 78: ...EQJW145 Heating controller Communication functions 78 7010015003 A Fr Sauter AG ...
Страница 82: ...EQJW145 Heating controller Faults 82 7010015003 A Fr Sauter AG ...
Страница 90: ...EQJW145 Heating controller Economy tips 90 7010015003 A Fr Sauter AG ...
Страница 92: ...EQJW145 Heating controller Resistance values for the Ni1000 sensors 92 7010015003 A Fr Sauter AG ...
Страница 94: ...EQJW145 Heating controller Dimension drawing 94 7010015003 A Fr Sauter AG ...
Страница 100: ...EQJW145 Heating controller Technical data 100 7010015003 A Fr Sauter AG ...