3.3.4
List of SERVice parameters
Parameter
Description
Range
Step value
SP01
Software version Y.XX (read only)
SP02
0
Device status (error coding) (read only)
1
SP03
View logbook
-
SP04
0
Software reset
0 = no Reset
1 = factory setting for SE + CO parameters
2 = factory setting for switching commands
3 = factory setting for SE- + CO para
switching commands
0...3
1
SP05
0
Manual mode
0 = manual mode not enabled
1 = manual mode enabled
0...1
1
SP06
1
Control model
1 = one control valve on the primary side
2 = one control valve on the secondary side
3 = two control valves on the primary side
0...3
1
SP07
0
Effect of binary / pulse input (terminals 21, 22)
0 = HK in back-up mode if contact is closed.
1 = HK in reduced mode if contact is closed.
2 = HK in nominal mode if contact is closed.
3 = Pulse input for quantity metering
4 = Seepage limitation
5 = Input for fault signal
0…5
1
SP08
0
Room temperature recording
0 = no room temperature recording
1 = connect room sensor
2 = connect EGS52/15 or EGT 333 with room sensor
3 = connect EGS52/15 or EGT 333 without room
sensor
4 = MOD1,2: 2nd flow sensor for DHW (SP49 = 2)
0...4
1
SP09
0
Connect room temperature
0 = not enabled
1 = enabled if TRi > TRs
2 = enabled if TRi < TRs
3 = enabled if TRi <> TRs
0...3
1
SP10
20
Scanning time for room temperature if connected /[min]
1…100
1
SP11
0
Correction to room temperature TRi in K
-6.0...+6.0
0.1
Содержание EQJW145
Страница 1: ...EQJW145 Heating controller Operating manual 7010015003 A R ...
Страница 8: ...EQJW145 Heating controller Symbols used in this manual 8 7010015003 A Fr Sauter AG ...
Страница 10: ...EQJW145 Heating controller General information 10 7010015003 A Fr Sauter AG ...
Страница 46: ...EQJW145 Heating controller Commissioning 46 7010015003 A Fr Sauter AG ...
Страница 78: ...EQJW145 Heating controller Communication functions 78 7010015003 A Fr Sauter AG ...
Страница 82: ...EQJW145 Heating controller Faults 82 7010015003 A Fr Sauter AG ...
Страница 90: ...EQJW145 Heating controller Economy tips 90 7010015003 A Fr Sauter AG ...
Страница 92: ...EQJW145 Heating controller Resistance values for the Ni1000 sensors 92 7010015003 A Fr Sauter AG ...
Страница 94: ...EQJW145 Heating controller Dimension drawing 94 7010015003 A Fr Sauter AG ...
Страница 100: ...EQJW145 Heating controller Technical data 100 7010015003 A Fr Sauter AG ...