EQJW145: Heating controller
Using the controller
84
7010015003 A
© Fr. Sauter AG
8.2.1
Control model 1
PI
2P
Fig. 7: EQJW 145 Control model 1
Weather-compensating control of the flow temperature (secondary) in
converter installations with DHW preparation (parallel circuit) with 2 charge
pumps, via an additional converter (tank charge system)
Main SERVice parameters (see also 3.3)
SP06
1
(Control model
)
SP08
1
(Room sensor connection)
SP09
3
(Room temperature connection enabled)
SP34
2
(DHW heating with separate charge pump using two
DHW sensor.
)
SP49
2
(Configurable output is used to activate a 2nd charge
pump)