EQJW145: Heating controller
Commissioning
44
7010015003 A
© Fr. Sauter AG
Device bus: EDB 100 digital room operating unit
If an EDB100 digital room operating unit is to be used, CP18 must be set to
1.
If an EDB 100 digital room operating unit is used, the actual value for the
room temperature is evaluated by the EDB 100. The measured values of
other room operating units or room sensors (see SP08) are ignored.
Device bus: EDB 100 digital room operating unit
The address of the EDB 100 room operating unit assigned to the controller
must be set at CP19.
SMS or Modbus via modem: automatic configuration
If the type of communication (selected with parameter CP02) specifies that a
modem is used, parameter CP20 is automatically assigned a value of 1.
Otherwise, CP20 has a value of 0 as the factory setting. If parameter CP20
has value 1, the connected modem is configured automatically.
SMS or Modbus via modem: modem dialling pause
Time between two dialling attempts. A pause of several minutes must be
observed between calls so that the telecoms network is not continuously
under pressure.
SMS or Modbus via modem: modem timeout
In case of a connection via modem, the connection is terminated by the
controller if no data exchange has taken place after this time has elapsed.
SMS or Modbus via modem: number of dialling attempts
The dialling attempts via modem to the provider or the control station are
repeated, observing the dialling pause (CP21), if the line is busy or if it is
impossible to make a connection for any other reason. When the number of
dialling attempts set at CP 23 is reached, however, no further attempts are
made at first and the modem status is shown as 'OFF'. The dialling attempts
counter is automatically reset at 12:00 hours and then the dialling attempts to
the BMS are made again.
SMS or Modbus via modem: send message even if error is rectified
If CP24 is set to 1, dialling will also take place if the fault has been rectified
and the controller is operating without faults again.
SMS via modem: language for error messages
This parameter is used to select the language that is used to send an SMS.
The numbers have the following meanings: 0 = German. 1 = French.
2 = English. 3 = Italian. 4 = Spanish
Modbus via modem: disable fault dialling
If CP26 is set to 1, there are no dialling attempts via modem to the BMS if a
fault occurs.
CP18
CP19
CP20
CP21
CP22
CP23
CP24
CP25
CP26
Содержание EQJW145
Страница 1: ...EQJW145 Heating controller Operating manual 7010015003 A R ...
Страница 8: ...EQJW145 Heating controller Symbols used in this manual 8 7010015003 A Fr Sauter AG ...
Страница 10: ...EQJW145 Heating controller General information 10 7010015003 A Fr Sauter AG ...
Страница 46: ...EQJW145 Heating controller Commissioning 46 7010015003 A Fr Sauter AG ...
Страница 78: ...EQJW145 Heating controller Communication functions 78 7010015003 A Fr Sauter AG ...
Страница 82: ...EQJW145 Heating controller Faults 82 7010015003 A Fr Sauter AG ...
Страница 90: ...EQJW145 Heating controller Economy tips 90 7010015003 A Fr Sauter AG ...
Страница 92: ...EQJW145 Heating controller Resistance values for the Ni1000 sensors 92 7010015003 A Fr Sauter AG ...
Страница 94: ...EQJW145 Heating controller Dimension drawing 94 7010015003 A Fr Sauter AG ...
Страница 100: ...EQJW145 Heating controller Technical data 100 7010015003 A Fr Sauter AG ...