Technical data
96
7010015003 A
© Fr. Sauter AG
relay outputs for final control element
permitted start-up current 7A (max. 1sec)
2 x normally open contacts, 230V/0.5A/cos
> 0.5
Interface:
electrical specification
interface protocols
RS485, 2-wire. similar to RS232
Modbus (slave, format Modbus RTU,
connection with control station, also possible
via modem), or alternatively, device bus for
connection to other devices. fault signalling
with modem DataMod10 via SMS/fax
Measuring accuracy
Better than
±
0.3 K @ 25°C
Time constant for processing measured values
approx. 10 sec for TA,
< 5 sec. for TR and TF
Cycle time
Valve runtime / 15
Neutral zone
< 0.5 K
Minimum pulse duration
250 msec
Pump after-run time
2 x Ty
Heating characteristic
Curved, without the influence of extraneous
heat (see SP41)
Summer/winter heating limit
ON equals summer
winter.
OFF equals winter
summer
On when TAged < TS/W – 1 K.
OFF when TAged > TS/W
TS/W adjustable
Zero-point correction for room temp
up to
±
6 K is possible
Zero-point correction for outside temp.
up to
±
9 K is possible
Zero-point correction for return temperature
up to
±
9 K is possible
Tab. 12: Overview of technical data
Содержание EQJW145
Страница 1: ...EQJW145 Heating controller Operating manual 7010015003 A R ...
Страница 8: ...EQJW145 Heating controller Symbols used in this manual 8 7010015003 A Fr Sauter AG ...
Страница 10: ...EQJW145 Heating controller General information 10 7010015003 A Fr Sauter AG ...
Страница 46: ...EQJW145 Heating controller Commissioning 46 7010015003 A Fr Sauter AG ...
Страница 78: ...EQJW145 Heating controller Communication functions 78 7010015003 A Fr Sauter AG ...
Страница 82: ...EQJW145 Heating controller Faults 82 7010015003 A Fr Sauter AG ...
Страница 90: ...EQJW145 Heating controller Economy tips 90 7010015003 A Fr Sauter AG ...
Страница 92: ...EQJW145 Heating controller Resistance values for the Ni1000 sensors 92 7010015003 A Fr Sauter AG ...
Страница 94: ...EQJW145 Heating controller Dimension drawing 94 7010015003 A Fr Sauter AG ...
Страница 100: ...EQJW145 Heating controller Technical data 100 7010015003 A Fr Sauter AG ...