EQJW145: Heating controller
Commissioning
7010015003 A
17
© Fr. Sauter AG
3.2.1
List of SERVice parameters
The following SERVice parameters can be reached on commissioning level.
Para-
meter
Description
Range
Step value
SP01
Software version Y.XX (read only)
SP06
1
Control model
1 = one control valve on the primary side
2 = one control valve on the secondary side
3 = two control valves on the primary side
0...3
1
SP15
40
Proportional band, PI controller in K
2...100
1
SP16
40
MOD3: Proportional band, PI controller in K (2nd control circuit)
2...100
1
SP19
120
Runtime for final control element in sec
30...960
15
SP20
180
Runtime for second final control element in sec
MOD1, 2: for diverter valve (SP34 = 3 or 4)
MOD3: for second control valve
30...960
15
SP34
1
Functions for domestic hot water
0 = not enabled.
1 = MOD 1, 2: with sep. charge pump using one DHW
sensor
2 = MOD 1, 2: with sep. charge pump using two DHW
sensors
3 = MOD 1, 2: with diverter valve using one DHW sensor
4 = MOD 1, 2: with diverter valve using two DHW
sensors
0…4
1
SP36
5
MOD 1, 2: Switching difference for domestic hot water in K
1...30
1
SP37
70
Maximum setpoint for increased DHW temperature/[°C]
10…90
1
SP38
10
Setpoint boost for domestic hot water in K
0…30
1
SP41
1.4
Slope of heating characteristic
0.2...5.0
0.1
SP60
0
Floor drying
0 = not enabled. 7d = enabled. 8 = malfunction
9 = successfully completed
0.7d.8.9 0.7d. 8.9
Tab. 1: SERVice parameter
An overview of the SERVice parameters and explanations for individual
SERVice parameters is given in these sections: 'List of SERVice parameters'
and 'Explanations for individual SERVice parameters'.
Содержание EQJW145
Страница 1: ...EQJW145 Heating controller Operating manual 7010015003 A R ...
Страница 8: ...EQJW145 Heating controller Symbols used in this manual 8 7010015003 A Fr Sauter AG ...
Страница 10: ...EQJW145 Heating controller General information 10 7010015003 A Fr Sauter AG ...
Страница 46: ...EQJW145 Heating controller Commissioning 46 7010015003 A Fr Sauter AG ...
Страница 78: ...EQJW145 Heating controller Communication functions 78 7010015003 A Fr Sauter AG ...
Страница 82: ...EQJW145 Heating controller Faults 82 7010015003 A Fr Sauter AG ...
Страница 90: ...EQJW145 Heating controller Economy tips 90 7010015003 A Fr Sauter AG ...
Страница 92: ...EQJW145 Heating controller Resistance values for the Ni1000 sensors 92 7010015003 A Fr Sauter AG ...
Страница 94: ...EQJW145 Heating controller Dimension drawing 94 7010015003 A Fr Sauter AG ...
Страница 100: ...EQJW145 Heating controller Technical data 100 7010015003 A Fr Sauter AG ...