Appendix D Event and Data Logging
79
The data recorder can record up to 16 data parameters per record in each
of 8 data log files. The list of parameters is configured individually for
each data log file.
Before configuring data log parameters in your device, you should
allocate memory for the data log and specify how many parameters each
record will contain. Parameters that are not included into the record will
be designated as not available.
To configure the data log parameters, select Memory/Log from the Meter
Setup menu, click on the Data Recorder tab, and then select a data log
you want to configure.
To specify parameters for the data log:
1. Click on the “Group” box for the first parameter and select
a data group that contains the desired parameter.
2. Click on the “Parameter” box for the first parameter and
select a parameter from the list.
3. Select the other parameters in the same manner. For
your convenience, when you open the “Group” box for
the next parameter, PAS highlights the same group as in
your previous selection. If you select this group again,
PAS will automatically update the “Parameter” box with
the next parameter in the group.
Data logs #1 and #2 are preset at the factory for periodic recording of the
standard power quantities. Their default data log configuration is shown in
the following table.
Data Log #1
No. Parameter No.
Parameter
1 V1
9 Total
kVA
2 V2
10 Total
PF
3 V3
11 V1
THD
4 I1
12 V2
THD
5 I2
13 V3
THD
6 I3
14 I1
THD
7
Total kW
15
I2 THD
8
Total kvar
16
I3 THD
Data Log #2
No. Parameter No.
Parameter
1
V1 Demand
9
kVA sliding demand
2
V2 Demand
10
kWh Import
3
V3 Demand
11
kWh Export
4
I1 Demand
12
kvarh Import
5
I2 Demand
13
kvarh Export
6 I3
Demand
14 In
7
kW import sliding demand
15
Frequency
8
kvar import sliding demand
16
Digital input #1