Appendix A Technical Specifications
69
Accuracy, %
Parameter
Full scale
Rdg FS Conditions
Range
Display resolution (%Rdg)
@ range
2
Harmonic active
power
0.36
×
PT
×
CT @ 120V input
1.2
×
PT
×
CT @ 690V input
1.5
2.0
1.0
1.0
PF = 1
|PF|
≥
0.5
3
-2,000,000 to
+2,000,000 kW
Direct wiring (PT=1):
0.001 kW @ 0.001kW to 9.999 kW
Wiring via PTs (PT>1):
0.001 MW @ 0.001MW to 9.999 MW
≤
0.1% @ 10.00 MW to 2000 MW
Harmonic apparent
power
0.36
×
PT
×
CT @ 120V input
1.2
×
PT
×
CT @ 690V input
1.5 1.0
3
0
to
2,000,000 kVA
Direct wiring (PT=1):
0.001 kVA @ 0.001kVA to 9.999 kVA
Wiring via PTs (PT>1):
0.001 MVA @ 0.001MVA to 9.999 MVA
≤
0.1% @ 10.00 MVA to 2000 MVA
Voltage & Current
harmonic angles,
degree
360°
0.6° + 0.5°
×
harmonic order
3
-180° to 180°
N/A
Active energy
Import & Export
Class 0.5S (IEC 687-1992-6)
0 to
999,999 MWh
1 kWh @ 1 to 999,999 kWh
10 kWh @ 1000 to 9,999.99 MWh
100 kWh @ 10,000 to 99,999.9 MWh
1MWh @ 100,000 to 999,999 MWh
Reactive energy
Import & Export
Under conditions of Class 1.0
(IEC 1036)
|PF|
≤
0.9
1
0 to
999,999 Mvarh
1 kvarh @ 1 to 999,999 kvarh
10 kvarh @ 1000 to 9,999.99 Mvarh
100 kvarh @ 10,000 to 99,999.9 Mvarh
1Mvarh @ 100,000 to 999,999 Mvarh