Chapter 4 Setup Menus
43
Table 4-10 User Selectable Options (
∗
default settings)
Code Parameter Option Description
P.cAL
Power calculation mode
1
rEAc
∗
nAct
Using reactive power
Using non-active power
roLL
Energy roll value
2
10.E4
10.E5
10.E6
10.E7
10.E8
10.E9
∗
10,000 kWh
100,000 kWh
1,000,000 kWh
10,000,000 kWh
100,000,000 kWh
1,000,000,000 kWh
Ph.En Phase
energy
measurements
diS
∗
, En
Enables/disables measurements
of energies per phase
Hr.En Harmonic
power/energy
measurements
diS
∗
, En
Enables/disables measurements
of harmonic powers and
energies
An.Ou
Analog output option (see
Section 4.5)
nonE
∗
0-20
4-20
0-1
-1-1
Disables analog output
0-20 mA
4-20 mA
0-1 mA
±
1 mA
An.EP
Analog expander option
(see Section 4.6)
nonE
∗
0-20
4-20
0-1
-1-1
Disables analog expander
0-20mA
4-20mA
0-1mA
±
1 mA
bAtt
Battery mode
OFF
∗
, On Switches the backup battery
OFF/ON
tESt
LED energy pulse test
mode
3
OFF
∗
Ac.Ei
rE.Ei
Disables energy pulse test mode
Runs Wh energy pulse test
Runs varh energy pulse test
1
Power calculation mode (P.cAL):
Mode 1: Reactive power calculation (rEAc)
Active power P and reactive power Q are measured directly and apparent
power:
2
2
Q
P
S
+
=
Mode 2: Non-active power calculation (nAct)
Active power is measured directly, apparent power S = V
×
I (where V, I =
RMS voltage and currents) and non-active power:
2
2
P
S
N
−
=
Mode 1 is recommended for electrical networks with low harmonic distortion
(voltage THD
<
5%, current THD
<
10%); Mode 2 is recommended for all other
cases.