Chapter 4 Setup Menus
37
voltage in other modes. See Section 4.1, Basic Setup Menu, for information on
setting the nominal voltage in your meter.
6
When the 4LN3 or 3LN3 wiring mode is selected, the voltages will be line-to-
neutral; for any other wiring mode they will be line-to-line voltages.
Table 4-8 Setpoint Actions (lower window, when middle window is Act)
Code Action
none No
action
1
rEL.1
Operate relay #1
2
rEL.2
Operate relay #2
2
Inc.Cn.1
Increment counter #1
Inc.Cn.2
Increment counter #2
Inc.Cn.3
Increment counter #3
Inc.Cn.4
Increment counter #4
Clr.Cn.1
Clear counter #1
Clr.Cn.2
Clear counter #2
Clr.Cn.3
Clear counter #3
Clr.Cn.4
Clear counter #4
Clr.Cnt Clear
all
counters
ELoG Event
log
3
dLoG.1
Data log #1
dLoG.2
Data log #2
dLoG.3
Data log #3
dLoG.4
Data log #4
dLoG.5
Data log #5
dLoG.6
Data log #6
dLoG.7
Data log #7
dLoG.8
Data log #8
32.LoG
Waveform log #1 (32 samples/cycle rate)
128.LoG
Waveform log #2 (128 samples/cycle rate)
Clr.Enr
Reset total energy
Clr.dnd
Reset all total maximum demands
Clr.P.dn
Reset power maximum demands
Clr.A.dn
Reset volt/ampere maximum demands
Clr.tEn
Reset TOU energy
Clr.tdn
Reset TOU maximum demands
Clr.LHi
Clear Min/Max registers
FG1.On
Set event flag #1
FG2.On
Set event flag #2
FG3.On
Set event flag #3
FG4.On
Set event flag #4
FG1.OFF
Clear event flag #1
FG2.OFF
Clear event flag #2
FG3.OFF
Clear event flag #3
FG4.OFF
Clear event flag #4
1
When a setpoint is operated, its status is always stored to the alarm status
register even if no action is assigned to the setpoint. The alarm status register can
be polled and cleared through communications.